APPX
Appendix 4 List of Link Special Relay (SB)
297
A
SB0040
Network type of own station
Stores the network type of the own station.
On: CC-Link IE Field Network
SB0043
Module operation mode of own
station
Stores the module operation mode of the own station.
Off: Online mode
On: Other than online mode
SB0044
Station setting 1 of own station
Stores the station type of the own station.
Off: Slave station (other than the master station)
On: Master station
SB0045
Station setting 2 of own station
Stores whether the station is local station or not when the own
station is a slave station.
Off: Other than a local station (submaster station, remote device
station, intelligent device station)
On: Local station
(Conditions)
• This relay is enabled when 'Station setting 1 of own station'
(SB0044) is off.
(Submaster
station only)
SB0046
Station number setting status of
own station
Stores the station number setting status.
Off: Station number set
On: Station number not set
If parameters are set using the engineering tool, this relay is always
OFF.
SB0047
Baton pass status of own station
Stores the baton pass status (transient transmission availability) of
the own station.
Off: Normal
On: Error
When this relay is turned on, the cause of the error can be checked
with 'Baton pass status of own station' (SW0047) and 'Cause of
baton pass interruption' (SW0048).
Depending on the link refresh timing, the update of 'Baton pass
status of own station' (SW0047) and 'Cause of baton pass
interruption' (SW0048) may be offset by one sequence scan.
SB0049
Data link error status of own station
Stores the data link error status of the own station.
Off: Normal
On: Error
When this relay is turned on, the cause of the error can be checked
with 'Cause of data link stop' (SW0049). Depending on the link
refresh timing, the update of 'Cause of data link stop' (SW0049)
may be offset by one sequence scan.
(Conditions)
• This relay is enabled when 'Baton pass status of own station'
(SB0047) is off.
• When 'Baton pass status of own station' (SB0047) is turned on,
data prior to error is held.
SB004A
CPU minor error status of own
station
Stores the minor error occurrence status of the CPU module on the
own station.
Off: No minor error
On: Minor error
SB004B
CPU moderate/major error status
of own station
Stores the moderate/major error occurrence status of the CPU
module on the own station.
Off: No moderate/major error
On: Moderate/major error
SB004C
CPU operating status of own
station
Stores the operating status of the CPU module on the own station.
Off: RUN
On: STOP, PAUSE, or moderate/major error
SB004D
Received parameter error
Stores the status of received parameter. (For the master station, this
relay stores the parameter status of the own station)
Off: Normal
On: Error
No.
Name
Description
Availability
Master station
(submaster
station)
Local station