130
2 PARAMETER SETTINGS
2.3 Basic Settings
Station Type
Select the station type (excluding the master station). Select the station type same as that
of the modules connected to the network.
• Remote I/O Station
• Remote Device Station
• Intelligent Device Station
• Local Station
• Sub-Mster Station
• Intelligent Device Station (Loop
Duplex)
(Default: Varies depending on the set
module)
RX/RY Setting
Assign RX/RY points. (
Page 16 Data flow and link device assignment)
Points can be assigned in increments of 16 (Start:
0H, End:
FH).
When "Station Type" is set to "Submaster Station", points can also be assigned for the
master station. (
To equally assign points or the same points, go to [Equal Assignment] or [Identical Point
Assignment] on the [CC IE Field Configuration] menu.
Points
• Master Station, Local Station,
Intelligent Device Station, Sub-
Master Station: 16 to 2048
• Remote Device Station: 16 to 128
• Remote I/O Station: 16 to 64
Device number
• 0H to 3FFFH
(Default: Varies depending on the set
module)
RWw/RWr Setting
Assign RWw/RWr points in increments of 4. (
Page 16 Data flow and link device
assignment)
When "Station Type" is set to "Submaster Station", points can also be assigned for the
master station. (
To equally assign points or the same points, go to [Equal Assignment] or [Identical Point
Assignment] on the [CC IE Field Configuration] menu.
Points
• Master Station, Local Station,
Intelligent Device Station, Sub-
Master Station: 4 to 1024
• Remote Device Station: 4 to 64
• Remote I/O Station: Cannot be set.
Device number
• 0H to 1FFFH
(Default: Varies depending on the set
module)
Reserved/Error Invalid
Station/System
Switching Monitoring
Target Station
Set this item to set the slave station as a reserved station, error invalid station, or system
switching monitoring target station.
However, the item cannot be set for the submaster station.
• No Setting: The slave station is connected to the network.
• Reserved Station: The slave station is reserved for future expansion. By reserving a
slave station, link device assignment will not change even if the slave station is added or
the reservation is canceled. Therefore, the program needs not to be modified. Physical
connection of the slave station is not required.
• Error Invalid Station: Even if a slave station is disconnected during data link, the master
station will not detect the slave station as a faulty station.
• System Switching Monitoring Target Station: Select this item for the slave station whose
continuous communication is desired first in case of a communication error. A maximum
of two devices can be set on one network only when "RJ71GF11-T2 (MR)" is selected for
the module name of the master station.
• No Setting
• Reserved Station
• Error Invalid Station
• System Switching Monitoring Target
Station
(Default: No Setting)
Pairing
When "RJ71GF11-T2 (SR)" or "RJ72GF15-T2 (SR)" is set on the network configuration,
stations set for pairing are displayed.
Network Synchronous
Communication
Select whether to synchronize the slave station using the CC-Link IE Field Network
synchronous communication function.
When "Synchronous" is selected and the master station is not set as a target module of the
inter-module synchronization in "Inter-module Synchronization Setting" in the [Inter-module
Synchronization Setting] tab of the "System Parameter" window, an error will occur in the
master/local module.
• Asynchronous
• Synchronous
(Default: Asynchronous)
Alias
Enter the name of a device if required.
The name entered is displayed in "Network Status" of the CC-Link IE Field diagnostics.
For the extension module of the remote device station, the name is not displayed in the CC-
Link IE Field Network diagnostics even if entered.
Up to 8 one-byte characters
(Default: Blank)
Comment
Information entered in "Comment1" on the "Properties" window displayed by right-clicking
the module in the list of stations or the network map is displayed.
Up to 32 one-byte characters
(Default: Blank)
Station-specific mode
setting
Set the station-specific mode of the slave station. This setting is available only when the
slave station supports the station-specific mode.
The setting varies depending on the
set module.
Module List
The slave stations are listed. Drag the modules from "Module List" to the list of stations or
the network map to set the information of the slave stations into the master station.
Item
Description
Setting range