15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
1487
15
+4
Target network number
Specify the network number of the target station.
• 1 to 239 (Network number)
1 to 239
User
+5
Target station number
Specify the station number of the target station.
(1) Station number specification
[Ethernet or CC-Link IE Controller Network]
• 0001H to 0078H (1 to 120): Station number
[CC-Link IE Field Network]
• 007DH (125): Master station
• 007EH (126): Master operating station
• 0001H to 0078H (1 to 120): Local station, intelligent device station, submaster
station
(2) Group number specification
[Ethernet or CC-Link IE Controller Network]
0081H to 00A0H: All stations with group numbers 01H to 20H
(Can be set when the execution type specified by (s1) is "0: No arrival
acknowledgment")
(3) All-station specification
00FFH: All stations of target network number (broadcast (excluding the own station))
(Can be set when the execution type specified by (s1) is "0: No arrival
acknowledgment")
0001H to 0078H,
007DH, 007EH,
0081H to 00A0H,
00FFH
User
+6
Not used
+7
Number of resends
(retries)
Effective when the execution type specified by (s1) is "1: Arrival acknowledgment
used".
■
Before instruction execution
Specify the number of resends to be performed if the instruction is not completed
within the monitoring time specified by (s1)+8.
• 0 to 15 (times)
■
At completion of instruction
The number of resends performed (result) is stored.
• 0 to 15 (times)
0 to 15
User/
system
+8
Arrival monitoring time
[CC-Link IE Controller Network or CC-Link IE Field Network]
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
• 0: 10s
• 1 to 32767: 1 to 32767s
0 to 32767
User
[Ethernet]
Specify the TCP resend timer value or greater for the monitoring time till completion
of processing. If processing is not completed within the monitoring time, the request
is resent by the number of resends specified in (s1)+7 (the number of resends).
• 0 to (TCP resend timer value): The TCP resend timer value is assumed as the
monitoring time.
• (TCP resend timer value + 1) to 16383: (TCP resend timer value + 1) to 16383s
0 to 16383
User
+9
Send data length
Specify the number of send data from (s2) to (s2)+n. (No information is stored if an
error is detected in the own station.)
■
Sending to RCPU, QCPU, or LCPU
• 1 to 960 (words)
■
Sending to QnACPU
• 1 to 480 (words)
1 to 960, 1 to 480
User
+10
Not used
+11
Clock setting flag
The validity status (valid or invalid) of the data in (s1)+12 and later is stored.
Note that the data in (s1)+12 and later is not cleared even when the instruction is
completed successfully.
• 0: Invalid
• 1: Valid
System
+12
Clock data
(Set only in an
abnormal state)
Upper 8 bits: Month (01H to 12H)
Lower 8 bits: Lower 2 digits of year (00H to 99H)
System
+13
Upper 8 bits: Hour (00H to 23H)
Lower 8 bits: Day (01H to 31H)
System
+14
Upper 8 bits: Second (00H to 59H)
Lower 8 bits: Minute (00H to 59H)
System
+15
Upper 8 bits: Year (00H to 99H: Upper two digits of the year)
Lower 8 bits: Day of the week (00H (Sun.) to 06H (Sat.))
System
Operand: (s1)
Device
Item
Description
Setting range
Set by
Содержание MELSEC iQ-R Series
Страница 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Страница 34: ...32 MEMO ...
Страница 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Страница 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Страница 204: ...202 5 SEQUENCE INSTRUCTIONS 5 3 Output Instructions Operation error There is no operation error ...
Страница 470: ...468 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 472: ...470 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 479: ...6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions 477 6 Operation error There is no operation error ...
Страница 504: ...502 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 518: ...516 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 520: ...518 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 754: ...752 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 756: ...754 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 758: ...756 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 760: ...758 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 895: ...7 APPLICATION INSTRUCTIONS 7 16 Ramp Signal Instruction 893 7 Operation error There is no operation error ...
Страница 917: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 915 7 Operation error There is no operation error ...
Страница 919: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 917 7 Operation error There is no operation error ...
Страница 1415: ...13 SFC PROGRAM INSTRUCTIONS 13 1 SFC Control Instructions 1413 13 Operation error There is no operation error ...
Страница 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Страница 1795: ...25 TYPE CONVERSION FUNCTIONS 25 1 Converting BOOL to WORD 1793 25 Operation error There is no operation error ...
Страница 1805: ...25 TYPE CONVERSION FUNCTIONS 25 10 Converting WORD to DINT 1803 25 Operation error There is no operation error ...
Страница 1819: ...25 TYPE CONVERSION FUNCTIONS 25 21 Converting INT to DWORD 1817 25 Operation error There is no operation error ...
Страница 1950: ...1948 32 STRING FUNCTIONS 32 2 Extracting String Data From the Left Right Operation error There is no operation error ...
Страница 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Страница 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Страница 2082: ...2080 APPX Appendix 6 Process Control Program Examples 129 Set the default value of the loop tag ...
Страница 2093: ...APPX Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions 2091 A MEMO ...
Страница 2109: ......