1156
10 PID CONTROL INSTRUCTIONS
10.1 Overview
Helpful functions
During PID operation by using PID control instructions, bumpless transfer and manipulated value upper/lower limit control are
automatically executed.
Bumpless transfer
This function controls the manipulated value (MV) continuously when the control mode is switched from manual to automatic,
or vice-versa. When the mode is switched, data are transferred between the MV storage areas for manual mode and
automatic mode.
• From manual to automatic: MV in manual mode is transferred to the MV storage area for automatic mode.
• From automatic to manual: MV in automatic mode is transferred to the MV storage area for manual mode.
Switch the mode in I/O data. (
PID control is performed in each mode as described below.
• Automatic mode: The CPU module controls the target with the MV calculated by PID operation using the
PID control instructions.
• Manual mode: The CPU module controls the target with the MV calculated without performing PID
operation using the PID control instructions. Loops set in manual mode stores the process value (PV) in the
set value storage area every sampling cycle.
Manipulated value upper/lower limits control
This function controls the upper or lower limit of the manipulated value (MV) calculated by PID operation. The function is only
enabled in automatic mode and is not executed in manual mode.
The manipulated value (MV) calculated by PID operation can be limited within the range set by the manipulated value upper
limit (MVHL) and manipulated value lower limit (MVLL). The following figure shows the operation of the function.
The manipulated value upper limit (MVHL) and manipulated value lower limit (MVLL) can be set to each loop within the range
of -50 to 2050 or within any desired range. The following values are set by default.
• Manipulated value upper limit: 2000
• Manipulated value lower limit: 0
An error occurs if the MVHL is smaller than the MVLL.
(1) MV
AUTO
without limit control
EV
MVHL
MVLL
MV
AUTO
(1)
Содержание MELSEC iQ-R Series
Страница 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Страница 34: ...32 MEMO ...
Страница 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Страница 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Страница 204: ...202 5 SEQUENCE INSTRUCTIONS 5 3 Output Instructions Operation error There is no operation error ...
Страница 470: ...468 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 472: ...470 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 479: ...6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions 477 6 Operation error There is no operation error ...
Страница 504: ...502 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 518: ...516 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 520: ...518 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 754: ...752 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 756: ...754 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 758: ...756 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 760: ...758 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 895: ...7 APPLICATION INSTRUCTIONS 7 16 Ramp Signal Instruction 893 7 Operation error There is no operation error ...
Страница 917: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 915 7 Operation error There is no operation error ...
Страница 919: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 917 7 Operation error There is no operation error ...
Страница 1415: ...13 SFC PROGRAM INSTRUCTIONS 13 1 SFC Control Instructions 1413 13 Operation error There is no operation error ...
Страница 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Страница 1795: ...25 TYPE CONVERSION FUNCTIONS 25 1 Converting BOOL to WORD 1793 25 Operation error There is no operation error ...
Страница 1805: ...25 TYPE CONVERSION FUNCTIONS 25 10 Converting WORD to DINT 1803 25 Operation error There is no operation error ...
Страница 1819: ...25 TYPE CONVERSION FUNCTIONS 25 21 Converting INT to DWORD 1817 25 Operation error There is no operation error ...
Страница 1950: ...1948 32 STRING FUNCTIONS 32 2 Extracting String Data From the Left Right Operation error There is no operation error ...
Страница 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Страница 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Страница 2082: ...2080 APPX Appendix 6 Process Control Program Examples 129 Set the default value of the loop tag ...
Страница 2093: ...APPX Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions 2091 A MEMO ...
Страница 2109: ......