18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.5 Reading the Module Model Information of an Intelligent Device Station
1623
18
• When the read target module has a model name, the model name is stored in the 2nd word and later according to the
following rules.
Ex.
The following table lists examples of model names stored.
If the model name in the I/O assignment setting and that of the mounted module differ, the model name held
by the mounted module is stored.
• When the read target module does not have a model name, the character string is stored in the 2nd word and later
according to the following rules.
Ex.
The following table lists examples of character strings stored (module type).
The following table lists examples of character strings stored (number of points).
If the number of points in the I/O assignment setting and that of the mounted module differ, the number of
points of the mounted module is stored.
Operation error
• The name occupies nine words.
• The name is stored in ASCII characters.
• 00H is stored in the 18th character.
• If the number of characters is less than 17, 00H is stored in the remaining characters.
• The model name held by a module or a unit is stored. (Note that it may differ from the one written on the rating plate.)
Target module
Character string example (module type)
Remote head module
RJ72GF15-T2
I/O module
INPUT_16
Network module
RJ71EN71(E+E)
• The name occupies nine words.
• The name is stored in ASCII characters.
• 00H is stored in the 18th character.
• If the number of characters is less than 17, 00H is stored in the remaining characters.
• A character string consisting of a combination of "character string indicating the module type" and "character string indicating the number of points" is stored.
Target module
Model name example
Input module
INPUT_16
Output module
OUTPUT_32
I/O combined module
MIXED_64
Intelligent function module
INTELLIGENT_128
Number of points
Character string example (number of points)
16 points
_16
32 points
_32
48 points
_48
64 points
_64
128 points
_128
256 points
_256
512 points
_512
1024 points
_1024
Error code
((s)+1)
Description
D000H to DFFFH
MELSEC iQ-R CC-Link IE Field Network User's Manual (Application)
Содержание MELSEC iQ-R Series
Страница 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Страница 34: ...32 MEMO ...
Страница 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Страница 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Страница 204: ...202 5 SEQUENCE INSTRUCTIONS 5 3 Output Instructions Operation error There is no operation error ...
Страница 470: ...468 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 472: ...470 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 479: ...6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions 477 6 Operation error There is no operation error ...
Страница 504: ...502 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 518: ...516 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 520: ...518 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 754: ...752 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 756: ...754 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 758: ...756 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 760: ...758 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 895: ...7 APPLICATION INSTRUCTIONS 7 16 Ramp Signal Instruction 893 7 Operation error There is no operation error ...
Страница 917: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 915 7 Operation error There is no operation error ...
Страница 919: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 917 7 Operation error There is no operation error ...
Страница 1415: ...13 SFC PROGRAM INSTRUCTIONS 13 1 SFC Control Instructions 1413 13 Operation error There is no operation error ...
Страница 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Страница 1795: ...25 TYPE CONVERSION FUNCTIONS 25 1 Converting BOOL to WORD 1793 25 Operation error There is no operation error ...
Страница 1805: ...25 TYPE CONVERSION FUNCTIONS 25 10 Converting WORD to DINT 1803 25 Operation error There is no operation error ...
Страница 1819: ...25 TYPE CONVERSION FUNCTIONS 25 21 Converting INT to DWORD 1817 25 Operation error There is no operation error ...
Страница 1950: ...1948 32 STRING FUNCTIONS 32 2 Extracting String Data From the Left Right Operation error There is no operation error ...
Страница 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Страница 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Страница 2082: ...2080 APPX Appendix 6 Process Control Program Examples 129 Set the default value of the loop tag ...
Страница 2093: ...APPX Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions 2091 A MEMO ...
Страница 2109: ......