11 PROCESS CONTROL INSTRUCTIONS
11.2 I/O Control Instructions
1205
11
■
Loop tag past value memory
The system uses this area as a work area.
To start the control from the initial status, clear data by using a sequence program.
The loop tag past value memory occupies 32 words after the loop tag memory.
■
Execution cycle (
T)
Set the execution cycle (
T) in SD816 and SD817 in single-precision real number.
+20
+21
ML
Output lower
limit value
-10 to 110 [%]
Single-precision
real number
0.0
User
+48
+49
DML
Output variation
rate limit value
0 to 100 [%]
Single-precision
real number
100.0
User
+54
+55
I
Integral constant
0 to 999999 [s]
Single-precision
real number
10.0
User
+62
+63
MVP
MV internal
operation value
-999999 to 999999 [%]
Single-precision
real number
0.0
System
Operand: (d2)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
(d2)+116
ALM2
Alarm detection
2
MHA2, MLA2, DMLA2
0: No alarm
1: Alarm
System
Operand: (d2)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
b15
b2
b3
b1 b0
MHA2
MLA2
DMLA2
...
Содержание MELSEC iQ-R Series
Страница 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Страница 34: ...32 MEMO ...
Страница 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Страница 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Страница 204: ...202 5 SEQUENCE INSTRUCTIONS 5 3 Output Instructions Operation error There is no operation error ...
Страница 470: ...468 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 472: ...470 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 479: ...6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions 477 6 Operation error There is no operation error ...
Страница 504: ...502 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 518: ...516 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 520: ...518 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 754: ...752 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 756: ...754 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 758: ...756 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 760: ...758 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 895: ...7 APPLICATION INSTRUCTIONS 7 16 Ramp Signal Instruction 893 7 Operation error There is no operation error ...
Страница 917: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 915 7 Operation error There is no operation error ...
Страница 919: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 917 7 Operation error There is no operation error ...
Страница 1415: ...13 SFC PROGRAM INSTRUCTIONS 13 1 SFC Control Instructions 1413 13 Operation error There is no operation error ...
Страница 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Страница 1795: ...25 TYPE CONVERSION FUNCTIONS 25 1 Converting BOOL to WORD 1793 25 Operation error There is no operation error ...
Страница 1805: ...25 TYPE CONVERSION FUNCTIONS 25 10 Converting WORD to DINT 1803 25 Operation error There is no operation error ...
Страница 1819: ...25 TYPE CONVERSION FUNCTIONS 25 21 Converting INT to DWORD 1817 25 Operation error There is no operation error ...
Страница 1950: ...1948 32 STRING FUNCTIONS 32 2 Extracting String Data From the Left Right Operation error There is no operation error ...
Страница 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Страница 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Страница 2082: ...2080 APPX Appendix 6 Process Control Program Examples 129 Set the default value of the loop tag ...
Страница 2093: ...APPX Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions 2091 A MEMO ...
Страница 2109: ......