1036
7 APPLICATION INSTRUCTIONS
7.26 Timing Check Instructions
Processing details
• This instruction measures the period of time for which the start contact is ON in units of hour, and turns on the device
specified by (d2) when the accumulated ON time reaches the time (16-bit binary data) specified in (s).
• In (s), specify the period of time until the device specified by (d2) is turned on in units of hour.
• The measured current value in units of hour is stored in (d1).
• The measured current value of less than one hour (in units of second) is stored in (d1)+1.
• Even after the alarm output specified by (d2) turns ON, the measurement is continued.
• When (d1) reaches the maximum value (32767) and also (d1)+1 reached reaches the maximum value (3599), the
measurement is stopped.
• This instruction operates even if a negative value is set in the device specified by (d1).
• Changing clock data (including time adjustment by the daylight-saving time function) does not affect the operation of the
HOURM instruction.
Precautions
• In cases such as measuring the ON time from initial value or continuing to the measurement even after the current value
reaches the maximum value of 16 bits, clear (d1) to (d1)+1 if (d1) is specified with the device, or clear two elements if (d1)
is specified with the label.
• To avoid that timer measurement does not work normally, do not use this instruction in the initial execution type program,
interrupt program, fixed scan execution type program, and event execution type program.
Operation error
Error code
(SD0)
Description
3405H
The range specified by (s) is outside the following range.
0 to 32767
Содержание MELSEC iQ-R Series
Страница 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Страница 34: ...32 MEMO ...
Страница 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Страница 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Страница 204: ...202 5 SEQUENCE INSTRUCTIONS 5 3 Output Instructions Operation error There is no operation error ...
Страница 470: ...468 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 472: ...470 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 479: ...6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions 477 6 Operation error There is no operation error ...
Страница 504: ...502 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 518: ...516 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 520: ...518 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 754: ...752 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 756: ...754 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 758: ...756 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 760: ...758 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 895: ...7 APPLICATION INSTRUCTIONS 7 16 Ramp Signal Instruction 893 7 Operation error There is no operation error ...
Страница 917: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 915 7 Operation error There is no operation error ...
Страница 919: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 917 7 Operation error There is no operation error ...
Страница 1415: ...13 SFC PROGRAM INSTRUCTIONS 13 1 SFC Control Instructions 1413 13 Operation error There is no operation error ...
Страница 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Страница 1795: ...25 TYPE CONVERSION FUNCTIONS 25 1 Converting BOOL to WORD 1793 25 Operation error There is no operation error ...
Страница 1805: ...25 TYPE CONVERSION FUNCTIONS 25 10 Converting WORD to DINT 1803 25 Operation error There is no operation error ...
Страница 1819: ...25 TYPE CONVERSION FUNCTIONS 25 21 Converting INT to DWORD 1817 25 Operation error There is no operation error ...
Страница 1950: ...1948 32 STRING FUNCTIONS 32 2 Extracting String Data From the Left Right Operation error There is no operation error ...
Страница 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Страница 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Страница 2082: ...2080 APPX Appendix 6 Process Control Program Examples 129 Set the default value of the loop tag ...
Страница 2093: ...APPX Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions 2091 A MEMO ...
Страница 2109: ......