10 PID CONTROL INSTRUCTIONS
10.3 PID Control Instructions (Exact Differential)
1173
10
Processing details
• These instructions store the PID control data by the number of loops used that is set in the device number specified by (s)
and later altogether in the CPU module to enable PID control. (
• The PID control data are assigned as follows.
*1 m = (n-1)
10 + 2
• The number of device points used for PID control data setting is calculated by the following formula.
Number of device points = 2 + 10
n (n: number of loops used)
• Specify each data in binary.
• If the total number of device points for the number of loops used exceeds the last device number, an error occurs and no
processing is performed.
• If the PIDINIT(P) instruction is executed at two or more locations during a single scan, the setting value of the PIDINIT(P)
instruction executed nearest to the PIDCONT(P) instruction will be valid.
• Execute the PIDINIT(P) instruction before execution of the PIDCONT(P) instruction. PID control is disabled unless the
PIDINIT(P) instruction has been executed.
Operation error
Item
PID control data
Common to all loops
(s)+0
Number of loops used
(s)+1
Number of loops in one scan
For loop No.1 (10 words)
(s)+2
Operational expression selection
(s)+3
Sampling period (T
S
)
(s)+4
Proportional constant (K
P
)
(s)+5
Integral constant (T
I
)
(s)+6
Derivative constant (T
D
)
(s)+7
Filter coefficient (
)
(s)+8
Manipulated value lower limit (MVLL)
(s)+9
Manipulated value upper limit (MVHL)
(s)+10
Manipulated value variation rate limit (
MVL)
(s)+11
Process value variation rate limit (
PVL)
For loop No.n (10 words)
(s)+(m+0)
Operational expression selection
(s)+(m+1)
Sampling period (T
S
)
(s)+(m+2)
Proportional constant (K
P
)
(s)+(m+3)
Integral constant (T
I
)
(s)+(m+4)
Derivative constant (T
D
)
(s)+(m+5)
Filter coefficient (
)
(s)+(m+6)
Manipulated value lower limit (MVLL)
(s)+(m+7)
Manipulated value upper limit (MVHL)
(s)+(m+8)
Manipulated value variation rate limit (
MVL)
(s)+(m+9)
Process value variation rate limit (
PVL)
Error code
(SD0)
Description
3405H
Out-of-range data is set in the device specified by (s).
• The value set for the PID control data is out of the setting range.
• (Number of loops used) < (number of execution loops in one scan)
• (Manipulated value upper limit) < (Manipulated value lower limit)
Содержание MELSEC iQ-R Series
Страница 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Страница 34: ...32 MEMO ...
Страница 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Страница 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Страница 204: ...202 5 SEQUENCE INSTRUCTIONS 5 3 Output Instructions Operation error There is no operation error ...
Страница 470: ...468 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 472: ...470 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 479: ...6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions 477 6 Operation error There is no operation error ...
Страница 504: ...502 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 518: ...516 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 520: ...518 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 754: ...752 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 756: ...754 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 758: ...756 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 760: ...758 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 895: ...7 APPLICATION INSTRUCTIONS 7 16 Ramp Signal Instruction 893 7 Operation error There is no operation error ...
Страница 917: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 915 7 Operation error There is no operation error ...
Страница 919: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 917 7 Operation error There is no operation error ...
Страница 1415: ...13 SFC PROGRAM INSTRUCTIONS 13 1 SFC Control Instructions 1413 13 Operation error There is no operation error ...
Страница 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Страница 1795: ...25 TYPE CONVERSION FUNCTIONS 25 1 Converting BOOL to WORD 1793 25 Operation error There is no operation error ...
Страница 1805: ...25 TYPE CONVERSION FUNCTIONS 25 10 Converting WORD to DINT 1803 25 Operation error There is no operation error ...
Страница 1819: ...25 TYPE CONVERSION FUNCTIONS 25 21 Converting INT to DWORD 1817 25 Operation error There is no operation error ...
Страница 1950: ...1948 32 STRING FUNCTIONS 32 2 Extracting String Data From the Left Right Operation error There is no operation error ...
Страница 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Страница 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Страница 2082: ...2080 APPX Appendix 6 Process Control Program Examples 129 Set the default value of the loop tag ...
Страница 2093: ...APPX Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions 2091 A MEMO ...
Страница 2109: ......