10 PID CONTROL INSTRUCTIONS
10.1 Overview
1155
10
I/O data
I/O data consists of input data, such as the set value (SV) and process value (PV), which are set to perform PID operation,
and output data, such as operation results. The I/O data can be set to a word device area with any numbers. Note that all the
data for the number of loops used must be set in the area with consecutive device numbers.
For data assignment, refer to the following.
• Inexact differential: Page 1163 S(P).PIDCONT
• Exact differential: Page 1174 PIDCONT(P)
The I/O data area is divided into two areas: data area assigned for each loop and work area used by the system.
*1 When the PID limit is restricted
*2 When the PID limit is not restricted
Item
Description
Setting range
Remarks
Set value
SV
A target value in PID control
0 to 2000
In the case of *1, if the SV is out of the
valid range, it will be converted as
follows.
• If the value is smaller than 0, 0 is
used.
• If the value is bigger than 2000, 2000
is used.
-32768 to 32767
Process value
PV
A feedback data from the control target to the A/D
converter module
-50 to 2050
In the case of *1, if the PV is out of the
valid range, it will be converted as
follows.
• If the value is smaller than -50, -50 is
used.
• If the value is bigger than 2050, 2050
is used.
-32768 to 32767
Automatic
manipulated value
MV
A manipulated value calculated by PID operation. The
value is output from the D/A converter module to the
control target.
-50 to 2050
-32768 to 32767
Process value after
filtering
PVf
A process value calculated by the following operational
expression
PV
fn
= PV
n
+
(PV
fn-1
- PV
n
)
-50 to 2050
-32768 to 32767
Manual manipulated
value
MV
MAN
Data output from the D/A converter module in manual
mode
-50 to 2050
In the case of *1, if the MV
MAN
is out of
the valid range, it will be converted as
follows.
• If the value is smaller than -50, -50 is
used.
• If the value is bigger than 2050, 2050
is used.
-32768 to 32767
Manual/automatic
selection
MAN/
AUTO
Select the type of output data to the D/A converter
module: manual manipulated value or automatic
manipulated value. In manual mode, the automatic
manipulated value remains unchanged.
0: Automatic
manipulated value
1: Manual
manipulated value
An error occurs if the set value is other
than 0 or 1, and PID operation of the
corresponding loop is not executed.
Alarm
ALARM
Checks whether the variation rate of the automatic
manipulated value (MV) or process value (PV) is within
the valid range or not. Once the value is set, it is held
until the CPU module is reset.
(1) If the PV is out of the limited range, 1 is set to b0.
(2) If the MV is out of the limited range, 1 is set to b1.
b15
b0
(1)
(2)
...
Содержание MELSEC iQ-R Series
Страница 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Страница 34: ...32 MEMO ...
Страница 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Страница 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Страница 204: ...202 5 SEQUENCE INSTRUCTIONS 5 3 Output Instructions Operation error There is no operation error ...
Страница 470: ...468 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 472: ...470 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 479: ...6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions 477 6 Operation error There is no operation error ...
Страница 504: ...502 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 518: ...516 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 520: ...518 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 754: ...752 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 756: ...754 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 758: ...756 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 760: ...758 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 895: ...7 APPLICATION INSTRUCTIONS 7 16 Ramp Signal Instruction 893 7 Operation error There is no operation error ...
Страница 917: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 915 7 Operation error There is no operation error ...
Страница 919: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 917 7 Operation error There is no operation error ...
Страница 1415: ...13 SFC PROGRAM INSTRUCTIONS 13 1 SFC Control Instructions 1413 13 Operation error There is no operation error ...
Страница 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Страница 1795: ...25 TYPE CONVERSION FUNCTIONS 25 1 Converting BOOL to WORD 1793 25 Operation error There is no operation error ...
Страница 1805: ...25 TYPE CONVERSION FUNCTIONS 25 10 Converting WORD to DINT 1803 25 Operation error There is no operation error ...
Страница 1819: ...25 TYPE CONVERSION FUNCTIONS 25 21 Converting INT to DWORD 1817 25 Operation error There is no operation error ...
Страница 1950: ...1948 32 STRING FUNCTIONS 32 2 Extracting String Data From the Left Right Operation error There is no operation error ...
Страница 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Страница 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Страница 2082: ...2080 APPX Appendix 6 Process Control Program Examples 129 Set the default value of the loop tag ...
Страница 2093: ...APPX Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions 2091 A MEMO ...
Страница 2109: ......