96
5 ACCESS FUNCTION USING NETWORK MODULE
5.5 Processing Time
5.5
Processing Time
This section shows the processing time of the cyclic transmission related to network module access.
For the processing time of the transient transmission, refer to the processing time of each function.
Link refresh time
The following shows the processing time of link refresh.
CC-Link IE Controller Network
The processing time when using CC-Link IE Controller Network is as follows.
•
β
T
: Total link refresh time (sending side)
•
β
R
: Total link refresh time (receiving side)
• KM1, KM2: Constant
• LB: Total number of points of link relays to be refreshed
*1
• LX: Total number of points of link inputs to be refreshed
*1
• LY: Total number of points of link outputs to be refreshed
*1
• LW: Total number of points of link registers to be refreshed
*1
*1 This is the total number of points of link devices set for the setting range of "Refresh Setting" and "Network Range Assignment"
("Network Configuration Settings"). The number of points assigned to a reserved station is not included.
Link refresh time can be calculated with the following formula depending on the number of assigned points of link devices.
CC-Link IE Field Network
The processing time when using CC-Link IE Field Network is as follows.
•
β
T
: Total link refresh time (sending side)
•
β
R
: Total link refresh time (receiving side)
• KM1, KM2: Constant
• RX: Total number of points of link inputs to be refreshed
*1
• RY: Total number of points of link outputs to be refreshed
*1
• RWw, RWr: Total number of points of link registers to be refreshed
*1
*1 This is the total number of points of link devices set for the setting range of "Refresh Setting" and "Network Range Assignment"
("Network Configuration Settings"). The number of points assigned to a reserved station is not included.
Link refresh time can be calculated with the following formula depending on the number of assigned points of link devices.
Network module mounting position
KM1
KM2
Main base unit
1.0
0.36
×
10
-3
Extension base unit
1.0
0.97
×
10
-3
Time
Formula
Link refresh time (ms)
β
T
,
β
R
= KM1 + KM2
×
{((LB + LX + LY)
÷
16) + LW}
Network module mounting position
KM1
KM2
Main base unit
1.0
0.41
×
10
-3
Extension base unit
1.0
0.99
×
10
-3
Time
Formula
Link refresh time (ms)
β
T
,
β
R
= KM1 + KM2
×
{((RX + RY)
÷
16) + RWw + RWr}
Содержание MELSEC iQ-R C R12CCPU-V
Страница 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Страница 2: ......
Страница 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Страница 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Страница 257: ...I 255 MEMO ...
Страница 261: ......