Appendix 12 Calculation Method for Heat Generation of C Controller Modules
Appendix 12
Calculation Method for Heat Generation
of C Controller Modules
The temperature inside the control panel in which a C Controller module is installed must be 55
or lower, which is the
operating ambient temperature of a C Controller module. Therefore, it is required to know the average power consumption
(heat generation) of the equipment and devices installed in the control panel for the heat release design of the panel.
For details on the calculation method, refer to the following manual.
MELSEC iQ-R Module Configuration Manual
It should be noted that the terms in the left column shall be replaced with the one in the right column.
Term
Replaced term
Programmable controller
C Controller module
Programmable controller system
C Controller system