Appendix 1 Error Code List
191
A
2520H
Invalid interrupt
Even though an interrupt was requested,
there is no interrupt factor.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module, I/O module, intelligent
function module, or base unit. Please consult your
local Mitsubishi representative.
System
configuratio
n
information
At interrupt
occurrence
2521H
Invalid interrupt
Even though an interrupt was requested,
there is no interrupt factor.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module, I/O module, intelligent
function module, or base unit. Please consult your
local Mitsubishi representative.
At interrupt
occurrence
2522H
Invalid interrupt
An interrupt request from the module with
no interrupt setting has been detected.
• Review the interrupt setting in the module
parameter.
• Take measures so that no interrupt is requested
from the module with no interrupt setting exists in
the module parameter.
• Review the interrupt setting in the buffer memory
of the Intelligent function module.
System
configuratio
n
information
At interrupt
occurrence
2610H
Inter-module
synchronization
signal error
• An execution interval error of the
synchronous interrupt program was
detected.
• An inter-module synchronization error
was detected.
• When the CC-Link IE Field Network module is a
synchronous target unit between unit, check the
connection status of the cable of CC-Link IE Field
module.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module, I/O module, intelligent
function module, base unit, or extension cable.
Please consult your local Mitsubishi
representative.
Always
2611H
Inter-module
synchronization
signal error
An inter-module synchronization error was
detected.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module, I/O module, intelligent
function module, base unit, or extension cable.
Please consult your local Mitsubishi
representative.
System
configuratio
n
information
At power
ON, RESET,
or fixed
cycle
processing
execution
2630H
Multiple CPU
synchronization
signal error
• An execution interval error of the
synchronous interrupt program was
detected.
• A multiple CPU synchronization error
was detected.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module or base unit. Please
consult your local Mitsubishi representative.
Always
2631H
Multiple CPU
synchronization
signal error
A multiple CPU synchronization error was
detected.
• Take measures to reduce noise.
• Reset the CPU module. If the same error code is
displayed again, the possible cause is a hardware
failure of the CPU module or base unit. Please
consult your local Mitsubishi representative.
System
configuratio
n
information
At power
ON, RESET,
or fixed
cycle
processing
execution
3000H
Boot function
execution error
The boot setting in the memory card
parameters is incorrect.
Review the boot setting in the memory card
parameters.
Drive and
file
information
At power
ON or
RESET
3001H
Boot function
execution error
When the boot function was executed, the
file format processing failed.
Reset the CPU module and perform the boot
function again. If the same error code is displayed
again, the possible cause is a hardware failure of the
CPU module. Please consult your local Mitsubishi
representative.
Drive and
file
information
At power
ON or
RESET
3004H
Boot function
execution error
When the boot function was executed, the
CPU built-in memory capacity was
exceeded.
• Review the boot setting.
• Delete unnecessary files in the CPU built-in
memory.
Drive and
file
information
At power
ON or
RESET
Error
code
Error name
Error details and cause
Corrective action
Detailed
informati
on
Diagnosti
c timing
Содержание MELSEC iQ-R C R12CCPU-V
Страница 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Страница 2: ......
Страница 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Страница 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Страница 257: ...I 255 MEMO ...
Страница 261: ......