![Mitsubishi Electric MELSEC iQ-R C R12CCPU-V Скачать руководство пользователя страница 113](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-c-r12ccpu-v/melsec-iq-r-c-r12ccpu-v_user-manual_239137113.webp)
6 Ethernet COMMUNICATION FUNCTIONS
6.2 Communication with SLMP
111
6
Command list
The available commands for C Controller modules are as follows.
Item
Comman
d
Subcommand
Description
Type
Operation
Device
Read
0401
00
1
Reads values from bit devices (consecutive device number) in 1-point units.
00
0
• Reads values from bit devices (consecutive device number) in 16-point units.
• Reads values from word devices (consecutive device number) in 1-word units.
00
3
Reads values from bit devices (consecutive device number) in 1-point units.
00
2
• Reads values from bit devices (consecutive device number) in 16-point units.
• Reads values from word devices (consecutive device number) in 1-word units.
Write
1401
00
1
Writes values to bit devices (consecutive device number) in 1-point units.
00
0
• Writes values to bit devices (consecutive device number) in 16-point units.
• Writes values to word devices (consecutive device number) in 1-word units.
00
3
Writes values to bit devices (consecutive device number) in 1-point units.
00
2
• Writes values to bit devices (consecutive device number) in 16-point units.
• Writes values to word devices (consecutive device number) in 1-word units.
Read Random
0403
00
0
Reads values from word devices in 1-word units or 2-word units by specifying device
number. Nonconsecutive device numbers can be specified.
00
2
Reads values from word devices in 1-word units or 2-word units by specifying device
number. Nonconsecutive device numbers can be specified.
Write Random
1402
00
1
Writes values to bit devices in 1-point units by specifying device number.
Nonconsecutive device numbers can be specified.
00
0
• Writes values to bit devices in 16-point units by specifying device number.
Nonconsecutive device numbers can be specified.
• Writes values to word devices in 1-word units or 2-word units by specifying device
number. Nonconsecutive device numbers can be specified.
00
3
Writes values to bit devices in 1-point units by specifying device number.
Nonconsecutive device numbers can be specified.
00
2
• Writes values to bit devices in 16-point units by specifying device number.
Nonconsecutive device numbers can be specified.
• Writes values to word devices in 1-word units or 2-word units by specifying device
number. Nonconsecutive device numbers can be specified.
Read Block
0406
00
0
Reads data by specifying multiple blocks as regarding one block as n-point of word
devices or bit devices (1-point is 16-bit). Nonconsecutive device numbers can be
specified.
00
2
Write Block
1406
00
0
Writes data by specifying multiple blocks as regarding one block as n-point of word
devices or bit devices (1-point is 16-bit). Nonconsecutive device numbers can be
specified.
00
2
Extend Unit
Read
0601
0000
Reads data in the buffer memory of an intelligent function module.
Write
1601
0000
Writes data in the buffer memory of an intelligent function module.
Remote
Control
Remote Run
1001
0000
Performs remote RUN to the access target module.
Remote Stop
1002
0000
Performs remote STOP to the access target module.
Remote Pause
1003
0000
Performs remote PAUSE to the access target module.
Remote Reset
1006
0000
Performs remote RESET to the access target module.
Read Type Name
0101
0000
Reads model and model code of the access target module.
File
Read Directory/
File
1810
0040
Reads information list of the file.
Search Directory/
File
1811
0040
Reads fine number, file size, and existence of the specified file.
New File
1820
0040
Reserves the storage area in the specified file.
Delete File
1822
0040
Deletes files.
Copy File
1824
0040
Copies the specified file.
Change File State
1825
0040
Changes the file attribute.
Change File Date
1826
0040
Changes the file creation date.
Open File
1827
0040
Locks the file in order that the file content is not changed form other devices.
Read File
1828
0000
Reads the content of a file.
Write File
1829
0000
Writes content to a file.
Close File
182A
0000
Unlocks a file with open processing.
Содержание MELSEC iQ-R C R12CCPU-V
Страница 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Страница 2: ......
Страница 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Страница 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Страница 257: ...I 255 MEMO ...
Страница 261: ......