5 ACCESS FUNCTION USING NETWORK MODULE
5.4 Access Function of Each Network Module
5.4
Access Function of Each Network Module
The network module access function transmits data to the devices on the network via the network module controlled by a C
Controller module.
CC-Link IE Controller Network module
The following shows the functions to transmit data via a CC-Link IE Controller Network module.
Available access methods
The following access methods are available.
Access by link refresh
This method is used to access devices of a C Controller module from a user program using link refresh. Data in the device is
transmitted cyclically to another station by reading from/writing to link devices of a network module by link refresh.
*1 Link refresh cannot be performed for SB/SW. Use the direct access.
Transmission type
Access method
Cyclic transmission
Access by link refresh
Direct access
Transient transmission
Message communication
Access to devices on another station
ZR
W
D
M
B
LW
LB
LX
LY
SB
*1
SW
*1
CC-Link IE Controller
Network module
C Controller module
Device
· link relay
· link register
User program
Link device
Link
refresh
Access to devices
Link device
Содержание MELSEC iQ-R C R12CCPU-V
Страница 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Страница 2: ......
Страница 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Страница 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Страница 257: ...I 255 MEMO ...
Страница 261: ......