APPX
Appendix 1 Error Code List
181
A
1166H
TCP/IP send
failed
Data was not sent correctly with TCP/IP.
• Check the settings for connection with the target
device.
• Check the operation of the target device or
switching hub.
• Since there may be congestion of packets on the
line, send data after a certain period of time.
• Check if the connection cable is disconnected.
• Check that there is no connection failure with the
switching hub.
Always
1200H
Module
moderate error
A moderate error has been notified from an
intelligent function module.
Check the detailed information (system configuration
information) of the error by performing module
diagnostics using CW Configurator and remove the
error.
System
configuratio
n
information
Always
1210H
Module
moderate error
An inter-module synchronization signal
error has been notified from the intelligent
function module.
Check the detailed information (system configuration
information) of the error by performing module
diagnostics using CW Configurator and remove the
error.
System
configuratio
n
information
Always
1220H
Another CPU
module
moderate error
A moderate error has been notified from
another CPU module.
• Check the detailed information (system
configuration information) of the error by
performing module diagnostics using CW
Configurator, identify the error module, and
eliminate the error cause.
• Check the mounting status and reset status of
another CPU module.
System
configuratio
n
information
Always
1240H
Inter-module
synchronization
processing
error
• The execution interval of the inter-
module synchronous interrupt program
exceeded the setting value.
• The inter-module synchronous interrupt
program (I44) has not been completed
within the inter-module synchronization
cycle.
Check the detailed information (time information) of
the error by performing module diagnostics using
CW Configurator, and take any of the following
corrective actions.
• Review the process content of the inter-module
synchronous interrupt program to complete the
process within the interval specified in "Fixed
Scan Interval Setting".
• Modify the value specified to "Fixed Scan Interval
Setting" to an appropriate value.
Time
information
At interrupt
occurrence
1241H
Inter-module
synchronization
processing
error
• The execution interval of the inter-
module synchronous interrupt program
exceeded the setting value.
• A cycle, which was not executed, has
been detected by the inter-module
synchronous interrupt program (I44).
Review the interrupt prohibited section and program
of which interrupt priority is high in order that the
inter-module synchronous interrupt program can be
executed.
At interrupt
occurrence
1260H
Multiple CPU
synchronization
processing
error
• The execution interval of the multiple
CPU synchronous interrupt program
exceeded the setting value.
• The multiple CPU synchronous interrupt
program (I45) has not been completed
within the cycle of the multiple CPU fixed
cycle communication.
Check the detailed information (time information) of
the error by performing module diagnostics using
CW Configurator, and take any of the following
corrective actions.
• Review the process content of the multiple CPU
synchronous interrupt program in order to
complete the process within the interval specified
in "Fixed Scan Interval Setting".
• Modify the value specified to "Fixed Scan Interval
Setting" to an appropriate value.
Time
information
At interrupt
occurrence
1262H
Multiple CPU
synchronization
processing
error
• The execution interval of the multiple
CPU synchronous interrupt program
exceeded the setting value.
• The multiple CPU synchronous interrupt
program (I45) has not been completed
within an execution section of the
program.
Check the detailed information (time information) of
the error by performing module diagnostics using
CW Configurator, and take any of the following
corrective actions.
• Review the process content of the multiple CPU
synchronous interrupt program in order to
complete the process within the program
execution section .
• Modify the value specified to "Fixed Scan Interval
Setting" to an appropriate value.
Time
information
At interrupt
occurrence
1830H
Receive queue
full
Number of reception requests of transient
transmission exceeded upper limit of
simultaneously processable requests.
Lower the transient transmission usage frequency,
and then perform again.
Always
Error
code
Error name
Error details and cause
Corrective action
Detailed
informati
on
Diagnosti
c timing
Содержание MELSEC iQ-R C R12CCPU-V
Страница 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Страница 2: ......
Страница 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Страница 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Страница 257: ...I 255 MEMO ...
Страница 261: ......