90
Installation 3. Wiring
1 Applicable electric wire specifications
The following table shows applicable electric wire sizes
.
Section
Screw type
Specification of wire used
Tightening
torques
Terminal of main unit.
(Auxiliary power,
Voltage input,
Current input,
MODBUS
®
RTU
communication
terminal)
M3
・
Use crimping terminals: AWG26 to 14 (Connectable 2 wires)
Applicable crimping terminals:
0.6 to 0.8N
・
m
Outer Diameter
For M3 screw with an outer
diameter of less than 6.0mm.
Terminal of Optional
plug-in module
・
ME-4210-SS96
・
ME-0040C-SS96
・
ME-0052-SS96
Without screw
Single wire, Stranded wire: AWG24 to 14
Wire coating stripping length
:
10 to 11mm
(Stranded wire is bar terminal can be used in combination.)
Note: UL recognized corresponds, use according to the following
conditions.
・
Single wire, Stranded wire: AWG24 to 18
・
Bar terminal can be not used in combination.
Note: When using the bar terminal for insert 2 wire, please select
insertion length of 12 to 13mm.
-
2 Wiring of the main unit.
Be sure to securely tighten the terminal screws to the terminal block.
CAUTION
・
Please do not connect three or more electric wires to one terminal. This can cause heat and fire
due to imperfect contact.
・
If you are using bare crimped terminals, provide the insulation needed to cover exposed live parts
and prevent electric shock and short circuits (e.g., use insulated tubing).
3 Connection method of terminal of optional plug-in module.
①
Peel the cover of the electric wire tip or crimp the bar terminal.
②
With the lever pressed, insert the electric wire
and then release the lever for connection.
4 Checking
Check the following after connection.
□The electric wire is securely connected.
□There is no error in connection.
Electric wire
10 to 11mm
Bar terminal
for inset 2wire
12 to 13mm
Insert hole
Lever
Содержание ME96SSRA-MB
Страница 88: ...87 Installation 1 Dimensions ME96SSRA MB Optional Plug in Module ME 4210 SS96 ME 0040C SS96 ME 0052 SS96 ...
Страница 89: ...88 Installation 1 Dimensions Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...
Страница 98: ...97 Installation 4 Wiring Diagram Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...