3. Setting
27
3.4. Setting Menu 2: Communication Settings (Setting the CC-Link communication)
<Setting flow when with ME-0040C-SS96>
In the operation mode, press
+
simultaneously for 2 seconds or more, and the following operation
becomes available.
SET
RESET
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
Set the setting menu number to “2”.
(as shown in the right figure)
Setting Menu
Set the CC-Link station number.
Selectable station number:
1 to 64
②
CC-Link station
number
Set the CC-Link baud rate.
③
CC-Link baud rates
156kbps
625
k
bps
2.5Mbps
5Mbps
10Mbps
Set the CC-Link version according to the configuration of the
used CC-Link system.
④
CC-Link version
Version 1.10
Version 2.00
Select either of “Setting of CC-Link communication” or “Setting of MODBUS
®
RTU
communication.”
CC
Mb.rtu
(CC-Link communication)
(MODBUS
®
RTU communication)
When “MODBUS® RTU communication” is selected,
refer to
①
MODBUS®RTU Address at page 26.
Hereafter, CC-Link communication setting describes.
①
Communication
setting selection
Содержание ME96SSRA-MB