Features
This instrument measures the load status by inputting the secondary side of the VT and CT, and displays various
measurement values.
This instrument supports active energy: class 0.5S and harmonic measurement up to 19th.
This instrument enables measurement of integrated active energy divided into two time segments such as
peak/off-peak and day/night. (Periodic Active Energy)
This instrument enables measurement of the active energy in a block of any period (interval).( Rolling
Demand)
The password protection setting avoids undesired change of settings or deletion of measured data.
The instruments with transmission functions (MODBUS
®
RTU communication, CC-Link communication,
MODBUS® TCP communication) are able to transmit the measured data to superior monitoring devices.
(CC-Link communication: When the ME-0040C-SS96 optional plug-in module is installed)
(MODBUS® TCP communication: When the ME-0000MT-SS96 optional plug-in module is installed)
Using the logging function, measurement data can be backup even when the MODBUS®RTU
communication fails.
(Logging function: When the ME-0000BU-SS96 optional plug-in module is installed)
The instruments with analog/pulse output function are able to output key measurement factors (current,
voltage, active power, power-factor, and Active Energy) of the power receiving point alone and are optimum
for remote monitoring.(When the ME-4210-SS96 optional plug-in module is installed)
This instrument complies with the requirements of the CE marking, UL standards, KC mark, and FCC/IC.
MODBUS
®
is a registered trademark of SCHNEIDER ELECTRIC USA, INC in the United States.
Содержание ME96SSRA-MB
Страница 88: ...87 Installation 1 Dimensions ME96SSRA MB Optional Plug in Module ME 4210 SS96 ME 0040C SS96 ME 0052 SS96 ...
Страница 89: ...88 Installation 1 Dimensions Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...
Страница 98: ...97 Installation 4 Wiring Diagram Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...