57
4. Using Test Mode
Test mode includes functions that can be used for start-up of equipment.
The following table shows what can be done in the test mode.
Test menu
Description
1. Communication test
For models with a communication function, it is possible to monitor fixed numerical
data without measurement (voltage/current) input. Use this for checking with the host
system.
2. Alarm output/Digital output
operation test
For functions with alarm output, it is possible to confirm alarm output (digital point
output) without measurement (voltage/current) input. Use this for confirming
connection with the contacted device.
3. Zero span adjustment for
analog output
For functions with analog output, zero span adjustment can be done for analog output.
Adjust this when matching with the receiver side and when output changes.
4. Analog output operation test
For functions with analog output, it is possible to confirm analog output operation
without measurement (voltage/current) input. Use this for confirming connection with
the receiver.
5. Pulse output operation test
For functions with pulse output, it is possible to confirm pulse output operation without
measurement (voltage/current) input. Use this for confirming connection with the
receiver.
■
Test Procedure
①
Press for 2 seconds to move to the set value confirmation mode.
②
Select setting value confirmation menu number "9" by and .
③
Press
to move to test mode.
④
Execute tests using each test menu. (Refer to pages 58 to 62)
■
Test Mode Flow
(Note) The screen momentarily turns off.
Note
When moving the test mode, ME-0000BU-SS96 becomes power outage state not to be logging the test data.
Therefore, the system log of “Power failure occurred” is recorded in ME-0000BU-SS96 and COM of the LCD is
blinking.
Test menu 2
(Alarm output /Digital
output operation test)
Test menu 3
(Zero span adjustment
for analog test)
Test menu 4
(Analog output
operation test)
Test menu 5
(Pulse output
operation test)
Operation
mode
Test mode
+
-
+
-
+
-
+
-
+
-
+
-
SET
+
-
SET
SET
SET
Setting value
Confirmation
menu "9"
Test menu
End
(
Note
)
Test menu 1
(Communication
test)