3. Setting
54
3.17.Setting the Special Display Pattern P00
(hereafter same as the setting menu 1)
Note
1. The following measurement items cannot be set by the display pattern “P00.”
Set them separately in the “Setting menu 3”, “Setting menu 7” and “Setting menu 8.”
Reactive energy (imported LEAD), Reactive energy (exported LAG),
Reactive energy (exported LEAD), Harmonic current, Harmonic voltage,
Periodic active energy, Rolling demand, Digital input, Digital output, Operation time
2. The phases of current and voltage cannot be specified. Press the
button in the
operation mode for switching phases.
3. For the settings other than the 3-phase 4-wire setting, the following measurement items
cannot be set.
N-phase current, N-phase current demand, apparent power, apparent energy
Continued form the previous page
(
5
)
Set the display of the display 4-2.
Select “yES” by or and press .
When you do not want to display the display 2,
select “no” and press .
(
6
)
Set the upper stage of the display 4-2 to PF.
Select “PF” by or and press .
(
7
)
Set the upper stage of the display 4-2 to W.
Select “W” by or and press .
(
8
)
Set the lower stage of the display 4-2 to no display.
Set the unit code of the lower stage to no display
by
or and press
.
(
9
)
Set the display 4-3 to no display.
Select “no” by or and press .
Note: When the display 4-3 is set to no display, the
display 4-4 is also set to no display automatically.
+
-
SET
SET
SET
SET
SET
+
-
SET
+
-
SET
+
-
SET
+
-
SET
SET
③
VT / direct voltage
DISPLAY
Returns to the setting for
the upper stage of the
display 4-1.
PHASE
Содержание ME96SSRA-MB