3. Setting
24
3.2 Setting menu 1: Basic Settings (Setting the Phase Wire System, Display Pattern,
VT/Direct Voltage, CT Primary Current, etc.)
Set the CT.
Primary /
secondary
Current Setting
<
Set the secondary current
>
Note. CT is current transformers.
<
Set the primary current
>
Default Setting
:
5.0A
④
CT
current
・
From top digit, select the value of the flickering digit by and .
・
The setting digit can be moved to right by the .
・
The setting digit can be moved to left by the
.
・
Setting is available in range from 1.0A to 30000.0A
Less than 10A : Upper 2 digits setting
Over 10A : Upper 3 digits setting
※
Error display (E05) appears when set out of 1.0 to 30000.0A
range. After that, please press , review the setting value
and set it once again.
※
When over 10A set over upper 3 digits setting, the display appear switching
upper 3 digits setting.
・
Press at the lowest digit, the setting step will shift to the next one.
1A
5A
+
-
DISPLAY
SET
SET
SET
Continued form the previous page
(
2
)
When using VT
<
Set the secondary and primary voltages of the VT.
>
(
a
)
For 3-phase 4-wire(Phase to phase Voltage)
(
b
)
For 3-phase 3-wire (2CT, 3CT) or 1-phase 2-wire
(
phase to neutral voltage
)
<
Primary Voltage Settings
>
Default value
For 3-phase 4-wire
:
200V
(Phase to phase Voltage)
For 3-phase 3-wire or 1-phase 2-wire
:
10000V
(
phase to neutral voltage
)
・
From top digit, select the value of the flickering digit by and
・
The setting digit can be moved to right by
・
The setting digit can be moved to left by
・
Setting is available in range from
60V to 750000V
Less than 100V : Upper 2 digits setting
Over 100V : Upper 3 digits setting
※
Error display (E05) appears when set out of 60Vto750000V range.
After that, please press , review the setting value and set it once
Again.
※
When over 100V set over upper 3 digits setting, the display appear switching
upper 3 digits setting.
・
Press at the lowest digit, the setting step will shift to the next one.
63.5V
100V
110V
115V
120V
100V
110V
220V
+
-
SET
DISPLAY
SET
SET
SET
DISPLAY
Содержание ME96SSRA-MB
Страница 88: ...87 Installation 1 Dimensions ME96SSRA MB Optional Plug in Module ME 4210 SS96 ME 0040C SS96 ME 0052 SS96 ...
Страница 89: ...88 Installation 1 Dimensions Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...
Страница 98: ...97 Installation 4 Wiring Diagram Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...