Safety Precaution
CAUTION
■
Others
MODBUS
®
RTU
communication
T/R+,T/R-,SG,Ter terminals
maxDC35V
MODBUS
®
TCP
communication
Ethernet terninals
CC-Link
communication
DA,DB,DG terminals
Digital input
DI1,DI2,DI3,DI4,DI COM,DI+,DI-,
DI1+,DI1-,DI2+,DI2-,DI3+,DI3-,DI4+,DI4-,DI5+,DI5- terminals
Digital output
DO1+,DO1-,DO2+,DO2- terminals
Analog output
CH1+,CH1-,CH2+,CH2-,CH3+,CH3-,CH4+,CH4- terminals
Pulse/ Alarm output
C1A/A1,C1B/COM1,C2A/A2,C2B/COM2 terminals
Do not drop this instrument from high place. If you drop it and the display is cracked,
do not touch the liquid crystal or get it in your mouth. If the liquid crystal is touched,
wash it away at once.
Work under the electric outage condition when installing and wiring. It may cause
electric shock, electric burn injury or damage of the device.
When tapping or wiring, take care not to entering any foreign objects such as chips
and wire pieces into this instrument.
If the terminal wiring is pulled with a strong force, the
terminals
may detach. (Tensile
load: 39.2N or less)
When wiring in this instrument, be sure that it is done correctly by checking the
instrument
‘
s wiring diagram. Wrong wiring may cause failure of the instrument, a fire
or electric shock.
Use electrical wire sizes compatible with the rated current. Use of unsuitable sizes
may cause heat generation, which may lead to a fire.
Tighten the terminal screws with the specified torque and use the suitable pressure
connectors and suitable wire size. (Refer to page 90)
In order to prevent invasion of noise, do not bunch the control wires or communication
cables with the main circuit or power wire, or install them close to each other. The
distance between communicational signal lines, input signal lines and power lines, and
high voltage lines when running parallel to each other are shown below.
Conditions
Length
Below 600V, or 600A power lines
30cm or more
Other power lines
60cm or more
Protective conductor terminals for mains circuits shall be at least equivalent in
current-carrying capacity to the mains supply terminals.
If the protective conductor terminals are also used for other bonding purposes, the
protective conductor shall be applied first and secured independently of other
connections.
■
Matters concerning the precaution before use
Use the instrument in the specified usage environment and conditions.
The setting of this instrument is necessary before use it. Please read this manual carefully to ensure
correct setting.
Confirm the rating of this instrument, and supply power voltage within the specified range.