89
Installation 2. Mounting
1 Dimensions of mounting holes
The drilling dimensions of the panel are as shown in the right figure.
The product can be installed to a panel having a thickness of
1.6 to 4.0 mm.
2 Mounting position
The contrast of the LCD changes depending on the angle at which
it is viewed.
Mount the product in the easy viewable position.
3 Mounting and fixing
Mount the product to the panel of the main unit according to the following procedure.
4 Mounting the optional plug-in module
Mount the optional plug-in module to the main unit according to the following procedure.
①
Remove the optional cover.
②
Mount the optional plug-in module to the main unit.
Note
Protecting sheet
The LCD part is covered with a protecting sheet to avoid scratches to the LCD during
mounting of the panel. Before starting operation, remove the sheet. When removing the
sheet, the LCD may illuminate due to static electricity, but this is not a product failure. After
a while, the LCD goes off as it naturally discharges electricity.
Mounting position
To mount the product to the edge of the panel, check the space for wiring work before
determining the mounting position.
Optional plug-in module
Turn off the auxiliary power before mounting the optional plug-in module.
If the optional plug-in module is mounted during energization, the optional plug-in module
cannot be recognized on the main unit side.
In this case, turning on/restoring the auxiliary power or performing operation of “restarting
the instrument” allows the optional plug-in module to be recognized.
Engage the convex of the
optional plug-in module in
the groove of the main
unit.
①
Attach the mounting brackets to two areas
each in upper and lower parts of the main unit.
②
Tighten the screws of the mounting
brackets to fix them to the panel.
Screw type for mounting to the main unit: M3
Note
To avoid damage to the
panel and screws, do not
overtighten the screws.
The recommended torque
for this product is 0.3 N•m to
0.5 N•m (about half the
normal torque).
Tighten the upper and lower
screws evenly.