1 - 12
Chapter1 Outline of Synchronous Control
1.4.2 Starting/ending for synchronous control
Set the parameters for synchronous control for each output axis to start synchronous control.
The status changes to synchronous control after the parameters are analyzed at the start of
synchronous control, and the output axes synchronize with input axis operations.
Standby (0)
t
t
t
Md.407 Cam axis current value
per cycle
Md.26 Axis operation status
Md.20 Feed current value
Md.321 Synchronous encoder
axis current value per
cycle
Cd.380 Synchronous control
start (Target axis bit)
BUSY signal
Standby (0)
Analyzing (5)
Synchronous control (15)
Synchronous control system control data
Setting item
Setting details
Setting value
Default
value
Buffer memory
address
[Cd.380]
Synchronous control
start
• Synchronous control begins if the target
axis bit is turned ON.
• Synchronous control ends if the bit is
turned OFF during synchronous control.
Fetch cycle: Operation cycle
Set the target axis in 16bits.
(bit0: axis 1 to bit15: axis 16
(Note-1)
)
OFF : Synchronous control end
ON : Synchronous control start
0 36320
(Note-1): The range from axis 1 to 2 is valid in the 2-axis module, from axis 1 to 4 is valid in the 4-axis module, from axis 1 to 8 is valid in the
8-axis module, and from axis 1 to 16 is valid in the 16-axis module.
Starting method for synchronous control
Synchronous control can be started by turning the target axis bit from OFF to ON in
"[Cd.380] Synchronous control start" after setting the parameters for synchronous control.
"5: Analyzing" is set in "[Md.26] Axis operation status" at the synchronous control start, and
the parameters for synchronous control are analyzed. The BUSY signal turns ON after
completion of analysis, and "15: Synchronous control" is set in "[Md.26] Axis operation
status".
Start the input axis operation after confirming that "15: Synchronous control" is set in
"[Md.26] Axis operation status".
Ending method for synchronous control
Synchronous control can be ended by turning the target axis bit from ON to OFF in
"[Cd.380] Synchronous control start" after the input axis operation is stopped.
The BUSY signal turns OFF at the synchronous control end, and "0: Standby" is set in
"[Md.26] Axis operation status" at the output axis stop.
Synchronous control can also be ended by turning the target axis bit from ON to OFF in
"[Cd.380] Synchronous control start" during the input axis operation. However, it is
recommended to end after stopping the input axis operation since the output axis stops
immediately.
Refer to Section 1.4.3 "Stop operation of output axis" at the synchronous control end.
Содержание LD77MH
Страница 2: ......
Страница 48: ...1 16 Chapter1 Outline of Synchronous Control MEMO ...
Страница 84: ...2 36 Chapter 2 Input Axis Module MEMO ...
Страница 104: ...3 20 Chapter 3 Cam Function MEMO ...
Страница 168: ...4 64 Chapter 4 Synchronous Control MEMO ...
Страница 223: ...Appendix 7 Appendices 3 Create the cam data cam No 1 4 Set the synchronous parameter of the axis 1 ...
Страница 234: ...Appendix 18 Appendices MEMO ...
Страница 237: ......