65
Par
a
meter
Li
st
Parameter list
4
⎯
125
Terminal 2 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
⎯
126
Terminal 4 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
PI
D
co
nt
ro
l
127
PID control automatic switchover
frequency
0 to 400Hz, 9999
0.01Hz
9999
128
PID action selection
10, 11, 20, 21, 50, 51,
60, 61, 70, 71, 80, 81,
90, 91, 100, 101, 110,
111, 120, 121
1
10
129
PID proportional band
0.1 to 1000%, 9999
0.1%
100%
130
PID integral time
0.1 to 3600s, 9999
0.1s
1s
131
PID upper limit
0 to 100%, 9999
0.1%
9999
132
PID lower limit
0 to 100%, 9999
0.1%
9999
133
PID action set point
0 to 100%, 9999
0.01%
9999
134
PID differential time
0.01 to 10.00s, 9999
0.01s
9999
By
pa
ss
135
Electronic bypass sequence selection
0, 1
1
0
136
MC switchover interlock time
0 to 100s
0.1s
1s
137
Start waiting time
0 to 100s
0.1s
0.5s
138
Bypass selection at a fault
0, 1
1
0
139
Automatic switchover frequency from
inverter to bypass operation
0 to 60Hz, 9999
0.01Hz
9999
B
ack
la
sh
m
e
as
ur
es
140
Backlash acceleration stopping
frequency
0 to 400Hz
0.01Hz
1Hz
141
Backlash acceleration stopping time
0 to 360s
0.1s
0.5s
142
Backlash deceleration stopping
frequency
0 to 400Hz
0.01Hz
1Hz
143
Backlash deceleration stopping time
0 to 360s
0.1s
0.5s
⎯
144
Speed setting switchover
0, 2, 4, 6, 8, 10, 102,
104, 106, 108, 110
1
4
PU
145
PU display language selection
0 to 7
1
1
⎯
147
Acceleration/deceleration time
switching frequency
0 to 400Hz, 9999
0.01Hz
9999
148
Stall prevention level at 0V input
0 to 120%
0.1%
110%
C
u
rr
e
n
t d
e
te
ct
io
n
149
Stall prevention level at 10V input
0 to 120%
0.1%
120%
150
Output current detection level
0 to 120%
0.1%
110%
151
Output current detection signal delay
time
0 to 10s
0.1s
0s
152
Zero current detection level
0 to 150%
0.1%
5%
153
Zero current detection time
0 to 10s
0.01s
0.5s
⎯
154
Voltage reduction selection during
stall prevention operation
0, 1
1
1
⎯
155
RT signal function validity condition
selection
0, 10
1
0
⎯
156
Stall prevention operation selection
0 to 31, 100, 101
1
0
⎯
157
OL signal output timer
0 to 25s, 9999
0.1s
0s
Function Parameters
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting