252
Communication operation and setting
ANALOG VALUE
*1
R: Read only W: Read/Write (Commandable values not supported) C: Read/Write (Commandable values supported)
*2
If communication speed command source is except for NET, the setting value can be written, but not to be applied.
*3
When both
C42 (Pr. 934 )
and
C44 (Pr. 935 )
≠
"9999", setting range is smaller coefficient to larger coefficient of
C42 (Pr. 934 )
and
C44 (Pr. 935 )
.
Depending on a value, the writing value and the reading value may not be same at the minimum digit.
Object
Identifier
Object Name
Present Value
Access Type
*1
Description
Unit
1
Output frequency
R
Represents the output frequency monitor.
hertz (27)
2
Output current
R
Represents the output current monitor.
amperes (3)
3
Output voltage
R
Represents the output voltage monitor.
volts (5)
6
Running speed
R
Represents the running speed monitor.
revolution-per-
minute
(104)
8
Converter output
voltage
R
Represents the converter output voltage monitor.
volts (5)
14
Output power
R
Represents the output power monitor.
kilowatts (48)
17
Load meter
R
Represents the load meter monitor.
percent (98)
20
Cumulative
energization time
R
Represents the cumulative energization time
monitor.
hours (71)
23
Actual operation time
R
Represents the actual operation time monitor.
hours (71)
25
Cumulative power
R
Represents the cumulative power monitor.
kilowatt-hours (19)
52
PID set point
R
Represents the PID set point monitor.
no-units (95)
54
PID deviation
R
Represents the PID deviation monitor.
(minus display is available with reference to 0%,
0.1% increment)
no-units (95)
67
PID measured value 2
R
Represents the PID measured value 2 monitor.
no-units (95)
200
Alarm history 1
R
Represents the fault history 1 (the latest fault)
monitor.
no-units (95)
201
Alarm history 2
R
Represents the fault history 2 (second fault in past)
monitor.
no-units (95)
202
Alarm history 3
R
Represents the fault history 3 (third fault in past)
monitor.
no-units (95)
203
Alarm history 4
R
Represents the fault history 4 (fourth fault in past)
monitor.
no-units (95)
300
Speed scale
*2
C
Controls the ratio to the frequency command.
(Setting range: 0.00 to 100.00)
percent (98)
310
PID set point CMD
*2
C
Controls the PID set point.
This object is the PID set point during PID operation
if
Pr. 128 (Pr. 753)
= "60 or 61"
(Setting range: 0.00 to 100.00)
*3
no-units (95)
311
PID measured value
CMD
*2
C
Controls the PID measured value.
This object is the PID measured value during PID
operation if
Pr. 128 (Pr. 753)
= "60 or 61"
(Setting range: 0.00 to 100.00)
*3
no-units (95)
312
PID deviation CMD
*2
C
Controls the PID deviation.
This object is the PID deviation during PID operation
if
Pr. 128 (Pr. 753)
= "50 or 51"
(Setting range: -100.00 to 100.00)
percent (98)
398
Mailbox parameter
W
Access to the properties which are not defined as
objects are available.
no-units (95)
399
Mailbox value
W
no-units (95)
10007
Acceleration time
W
Sets
Pr.7 Acceleration time
seconds (73)
10008
Deceleration time
W
Sets
Pr.8 Deceleration time
seconds (73)