5.4 Correspondences between digital and actual characters
There are the following correspondences between the actual alphanumeric characters and the digital characters
displayed on the operation panel.
Operation Panel
Indication
E.LCI
FR-PU04
Fault 14
FR-PU07
Fault
FR-PU07-01
Lost mA Input
Name
4mA input fault
Description
When the analog input current stays at 2mA or lower for the time period set in
Pr.778 Current input check
filter
, the protective circuit activates, and the inverter output is shutoff. The function is available when
Pr.573
4mA input check selection
="2 or 3." This protective function is not available in the initial status.
(Refer to page 182 )
Check point
· Check if the wire used for the analog current input has a break.
· Check if the
Pr.778 Current input check filter
setting is too low.
Corrective action
· Check the wiring for the analog current input.
· Set the
Pr.778 Current input check filter
setting higher.
CAUTION
• If protective functions of E.ILF, E.PTC, E.PE2, E.CDO, E.IOH, E.SER, E.AIE, E.PID, E.PCH, E.LCI are activated when using
the FR-PU04, "Fault 14" appears.
Also when the faults history is checked on the FR-PU04, the display is "E.14".
• If faults other than the above appear, contact your sales representative.
Actual
Digital
0
1
2
3
4
5
6
7
8
9
Actual
Digital
A
B
C
E
F
G
H
I
J
L
D
Actual
Digital
M
N
O
o
P
T
U
V
r
-
S
Содержание 700 Series
Страница 11: ...MEMO ...
Страница 23: ...12 MEMO ...
Страница 341: ...330 MEMO ...
Страница 365: ...354 MEMO ...
Страница 379: ...368 MEMO ...
Страница 397: ...386 MEMO ...
Страница 414: ...403 MEMO ...