PID control
Output signals
Signal
Terminal
Used
Function
Description
Parameter Setting
Ou
tp
ut
FUP
Depending on
Pr. 190 to Pr.
196
Upper limit output
Output to indicate that the measured
value signal exceeded the upper limit
value
(Pr. 131)
.
Pr. 128
=20, 21, 60, 61, 120, 121
Pr. 131
≠
9999
Set 15 or 115 in any of
Pr. 190 to Pr.
196
.
FDN
Lower limit output
Output when the measured value signal
falls below the lower limit
(Pr. 132)
.
Pr. 128
=20, 21, 60, 61, 120, 121
Pr. 132
≠
9999
Set 14 or 114 in any of
Pr. 190 to Pr.
196
.
RL
Forward (reverse)
rotation direction
output
"Hi" is output to indicate that the output
indication of the parameter unit is forward
rotation (FWD), and "Low" to indicate that
it is reverse rotation (REV) or stop (STOP).
Set 16 or 116 in any of
Pr. 190 to Pr.
196
.
PID
During PID
control activated
Turns ON during PID control.
Set 47 or 147 in any of
Pr. 190 to Pr.
196
.
SLEEP
PID output
interruption
Turns ON when the PID output
interruption function is performed.
Pr. 575
≠
9999
Set 70 or 170 in any of
Pr. 190 to Pr.
196
.
Y48
PID deviation limit
Output when the absolute value of
deviation exceeds the limit value.
Pr. 553
≠
9999
Set 48 or 148 in any of
Pr. 190 to Pr.
196
.
Y49
During pre-
charge operation
Output during the pre-charge operation
Set 49 or 149 in any of
Pr. 190 to Pr.
196
.
Y50
During second
pre-charge
operation
Set 50 or 150 in any of
Pr. 190 to Pr.
196
.
Y51
Pre-charge time
over
Output when the pre-charged time
exceeds the time set in
Pr.764
or
Pr.769
.
Set 51 or 151 in any of
Pr. 190 to Pr.
196
.
Y52
Second pre-
charge time over
Set 52 or 152 in any of
Pr. 190 to Pr.
196
.
Y53
Pre-charge level
over
Output when the pre-charged amount
exceeds the set level in
Pr.763
or
Pr.768
.
Set 53 or 153 in any of
Pr. 190 to Pr.
196
.
Y54
Second pre-
charge level over
Set 54 or 154 in any of
Pr. 190 to Pr.
196
.
SE
SE
Output terminal
common
Common terminal for terminals assigned
to FUP signal, FDN signal, RL signal, PID
signal, SLEEP signal, and Y48 signal
*1
When 100 or larger value is set to any of
Pr. 190 to Pr. 196 (output terminal function selection)
, the terminal output has negative logic.
page 128 for details)
CAUTION
⋅
Changing the terminal function using any of
Pr. 178 to Pr. 189, 190 to Pr. 196
may affect the other functions. Please set
parameters after confirming the function of each terminal.