257
Communication operation and setting
4
Faults history
Fault code list
* Refer to the FR-F700 PLC function programming manual for details of the PLC function.
Model information monitor
Register
Definition
Read/Write
Remarks
40501
Fault history 1
Read/write
Being 2 bytes in length, the data is stored as
"H00
". Refer to the lowest 1 byte for the fault
code.
Performing write using the register 40501 batch-
clears the faults history. Set any value as data.
40502
Fault history 2
Read
40503
Fault history 3
Read
40504
Fault history 4
Read
40505
Fault history 5
Read
40506
Fault history 6
Read
40507
Fault history 7
Read
40508
Fault history 8
Read
Register
Definition
Read/Write
Remarks
44001 to
44010
Inverter type
Read
Reading inverter type in ASCII code.
"H20" (blank code) is set for blank area
Example of FR-F720-NA
H46, H52, H2D, H46, H37, H32, H30, H2D, H4E, H41, H20 ...... H20
44011 to
44013
Capacity
Read
Reading inverter capacity in ASCII code.
Data is read in increments of 0.1kW, and rounds down to 0.01kW
increments
"H20" (blank code) is set for blank area
Example
0.75K ............... " 7" (H20, H20, H20, H20, H20, H37)
Data
Description
H00
No fault
H10
OC1
H11
OC2
H12
OC3
H20
OV1
H21
OV2
H22
OV3
H30
THT
H31
THM
H40
FIN
H50
IPF
H51
UVT
H52
ILF
H60
OLT
H70
BE
H80
GF
H81
LF
H90
OHT
H91
PTC
HA0
OPT
HA1
OP1
HA2
OP2
HA4
E.16 *
HA5
E.17 *
Data
Description
HA6
E.18 *
HA7
E.19 *
HA8
E.20 *
HB0
PE
HB1
PUE
HB2
RET
HB3
PE2
HC0
CPU
HC1
CTE
HC2
P24
HC4
CDO
HC5
IOH
Data
Description
HC6
SER
HC7
AIE
HE4
LCI
HE5
PCH
HE6
PID
HF1
E.1
HF2
E.2
HF5
E.5
HF6
E.6
HF7
E.7
HFD
E.13
Data
Description