130
Function assignment of external
71
⎯
RO1
Commercial-power
supply side motor 1
connection RO1
Used when using advanced PID control
(pump function).
Pr. 575 to Pr. 591
72
⎯
RO2
Commercial-power
supply side motor 2
connection RO2
73
⎯
RO3
Commercial-power
supply side motor 3
connection RO3
74
⎯
RO4
Commercial-power
supply side motor 4
connection RO4
75
⎯
RIO1
Inverter side motor 1
connection RIO1
76
⎯
RIO2
Inverter side motor 2
connection RIO2
77
⎯
RIO3
Inverter side motor 3
connection RIO3
78
⎯
RIO4
Inverter side motor 4
connection RIO4
79
179
Y79
Pulse train output of
output power
Output in pulses every time the accumulated
output power of the inverter reaches the
Pr.799
setting.
Pr. 799
82
182
Y82
BACnet binary output
Control of binary output from BACnet is
available.
⎯
85
185
Y85
DC feeding
Output during power failure or under voltage
of AC power.
Pr. 30, Pr. 70
90
190
Y90
Life alarm
Output when any of the control circuit
capacitor, main circuit capacitor and inrush
current limit circuit or the cooling fan
approaches the end of its service life.
Pr. 255 to Pr. 259
91
191
Y91
Fault output 3
(power-OFF signal)
Output when a fault occurs due to the
internal circuit failure of inverter wiring
mistake.
⎯
92
192
Y92
Energy saving
average value
updated timing
Turned ON and OFF alternately every time
the power saving average value is updated
when the power saving monitor is used.
Cannot be set to
Pr. 195 and Pr. 196
(relay
output terminal).
Pr. 52, Pr. 54,
Pr. 158, Pr. 891 to
Pr. 899
93
193
Y93
Current average
value monitor signal
Average current value and maintenance
timer value are output as pulses.
Cannot be set to
Pr. 195 and Pr. 196
(relay
output terminal).
Pr. 555 to Pr. 557
94
194
ALM2
Fault output 2
Output when the fault occurs. Continues
outputting the signal during inverter reset
and stops outputting after reset is cancelled.
*2
⎯
95
195
Y95
Maintenance timer
signal
Output when
Pr. 503
rises to or above the
Pr.
504
setting.
Pr. 503, Pr. 504
96
196
REM
Remote output
Output to the terminal when a value is set to
the parameter.
Pr. 495 to Pr. 497
98
198
LF
Alarm output
Output when an alarm (fan failure or
communication error warning) occurs.
Pr. 121, Pr. 244
99
199
ALM
Fault output
Output when the fault occurs. The signal
output is stopped when the fault is reset.
⎯
9999
⎯
No function
⎯
⎯
⎯
*1
Note that when the frequency setting is varied using an analog signal or
of the operation panel (FR-DU07), the output of the SU (up to
frequency) signal may alternate ON and OFF depending on that varying speed and the timing of the varying speed due to acceleration/
deceleration time setting. (The output will not alternate ON and OFF when the acceleration/deceleration time setting is "0s".)
*2
When a power supply reset is performed, the fault output 2 signal (ALM2) turns OFF as soon as the power supply switches OFF.
Setting
Signal
Name
Function
Operation
Related
Parameters
Refer
to Page
Positive
Logic
Negative
Logic