102
Setting of acceleration/deceleration time
and acceleration/deceleration pattern
(2) Deceleration time setting
(Pr. 8, Pr. 20)
⋅
Use
Pr. 8 Deceleration time
to set the deceleration time required to reach 0Hz from
Pr. 20 Acceleration/deceleration
reference frequency
.
⋅
Set the deceleration time according to the following formula.
(3) Change the setting range and increments of the acceleration/deceleration time
(Pr. 21)
⋅
Use
Pr. 21
to set the acceleration/deceleration time and minimum setting range.
Setting
"
0
"
(initial value) ..................... 0 to 3600s (minimum setting increments 0.1s)
Setting
"
1
"
.......................................... 0 to 360s (minimum setting increments 0.01s)
(4) Set multiple acceleration/deceleration time (RT signal,
Pr. 44, Pr. 45, Pr. 147
)
⋅
The
Pr. 44
and
Pr. 45
settings become valid when the RT signal turns ON or the output frequency reaches the
value of
Pr. 147
setting or higher.
⋅
When "9999" is set in
Pr. 45
, the deceleration time becomes equal to the acceleration time
(Pr. 44)
.
⋅
By setting
Pr. 147
, acceleration/deceleration time can be automatically changed at turn-OFF of the RT signal.
(1) Acceleration time setting
(Pr. 7, Pr. 20)
⋅
Use
Pr. 7 Acceleration time
to set the acceleration time required to reach
Pr.
20 Acceleration/deceleration reference frequency
from 0Hz.
⋅
Set the acceleration time according to the following formula.
Example) How to find the setting value for
Pr. 7
when increasing the output
frequency to the maximum frequency of 50Hz in 10s with
Pr. 20
=
60Hz (initial setting) and
Pr. 13
= 0.5Hz.
Example) How to find the setting value for
Pr. 8
when decreasing the
output frequency from the maximum frequency of 50Hz in 10s
with
Pr. 20
= 120Hz and
Pr. 10
= 3Hz.
CAUTION
⋅
Changing the
Pr. 21
setting changes the acceleration/deceleration time setting
(Pr. 7, Pr. 8, Pr. 16, Pr. 44, Pr. 45)
.
(The
Pr. 611
Acceleration time at a restart
setting is not affected.)
<Example>
When
Pr. 21
= "0", setting "5.0" s in
Pr. 7
and "1" in
Pr. 21
automatically changes the
Pr. 7
setting to "0.5" s.
Pr. 147
setting
Acceleration/deceleration time
Description
9999 (initial value)
Pr. 7, Pr. 8
Acceleration/deceleration time is not
automatically changed.
0.00Hz
Pr.44, Pr. 45
Second acceleration/deceleration time is
applied from the start.
0.01Hz
≤
Pr. 147
≤
set frequency
Output frequency <
Pr. 147
:
Pr. 7, Pr. 8
Pr. 147
≤
output frequency:
Pr. 44, Pr. 45
Acceleration/deceleration time is automatically
changed. *
Set frequency <
Pr. 147
Pr. 7, Pr. 8
Not changed as the frequency has not reached
the switchover frequency.
* Even if the output frequency is lower than the
Pr. 147
setting, the acceleration/deceleration time is changed to the second acceleration/
deceleration time by the RT signal.
Acceleration
time setting
=
Pr.20
×
Acceleration time from stop to
maximum operating frequency
Maximum operating
frequency -
Pr. 13
Running
frequency
Acceleration
time
Deceleration
time
Time
Pr.20
Pr.7
Pr.8
Output
frequency
(Hz)
(60Hz)
Pr.7
=
60Hz
×
10s
12.1s
50Hz - 0.5Hz
Deceleration
time setting
=
Pr. 20
×
Deceleration time from maximum
operating frequency to stop.
Maximum operating
frequency -
Pr. 10
Pr. 8
=
120Hz
×
10s
25.5s
50Hz - 3Hz
Set frequency
Pr.147
setting
Time
Output
frequency
(Hz)
Slope set
by
Pr.7
Slope set
by
Pr.44
Slope set
by
Pr.44
(Pr.45)
Slope set
by
Pr.8
Acceleration time
Deceleration time
Содержание 700 Series