23
Installation
Warning
Do not change jumper settings with power applied. Remove
line voltage or disable the drive before changing jumper
settings. Failure to follow these instructions may result in
damage to the drive or motor or serious injury.
Jumper settings
For NRGD05-series jumper locations, refer to Figure 10
(page 25). For NRGD10-series jumper locations, refer to
Figure 11 (page 26).
Tach-generator feedback voltage select (J501)
NOTE:
This jumper setting is applicable only if J502 and J503
are set for tach-generator feedback. It is otherwise inoperative.
Jumper terminals 1 and 2 on J501 as shown if the tach-generator
voltage range is 7.5–20 volts/1000 RPM. Jumper terminals 2 and
3 if the voltage range is 50–100 volts/1000 RPM. The factory
(default) setting is 7.5–20 volts/1000 RPM (terminals 1 and 2).
See Figure 12, page 27, for settings.
Feedback select (J502/J503)
Jumper terminals 1 and 2 on J502 and J503 as shown if the
feedback selected is from the motor armature. Jumper terminals 2
and 3 on J502 and J503 if the feedback is from a tach-generator.
The factory (default) setting is motor armature feedback
(terminals 1 and 2). See Figure 12, page 27, for settings.
250-0281.qxd 4/4/01 11:16 AM Page 23
Содержание NRGD-4Q Series
Страница 9: ...vii Regenerative Drives Figure 1 Four Quadrant Operation...
Страница 12: ...x Notes...
Страница 15: ...3 Dimensions Figure 2 NRGD05 Series Dimensions ALL DIMENSIONS IN INCHES MILLIMETERS...
Страница 16: ...4 Dimensions Figure 3 NRGD10 Series Dimensions ALL DIMENSIONS IN INCHES MILLIMETERS...
Страница 17: ...5 Dimensions Figure 4 Heat Sink Dimensions for NRGD10 Series Drives...
Страница 33: ...21 Installation Figure 8 Regen Dump Circuit Connections To NRGD Drives...
Страница 57: ...45 Figure 15 Connection to DLC600 and PCM4 Application Notes Connection to other Minarik devices...
Страница 78: ...Notes...