32
NRGD–4Q drives have nine user-adjustable trimpots. Each drive
is factory calibrated to its maximum horsepower rating. Readjust
the calibration trimpot settings to accommodate lower horsepower
motors.
With the exception of the TACH trimpot, all adjustments increase
with CW rotation, and decrease with CCW rotation. The TACH
trimpot increases with CCW rotation, and decreases with CW
rotation. Use a non-metallic screwdriver for calibration. Each
trimpot is identified on the printed circuit board.
Warning
Dangerous voltages exist on the drive when it is powered,
and up to 30 seconds after power is removed and the motor
stops. When possible, disconnect the voltage input from the
drive before adjusting the trimpots. If the trimpots must be
adjusted with power applied, use insulated tools and the
appropriate personal protection equipment. BE ALERT.
High voltages can cause serious or fatal injury.
Calibration
250-0281.qxd 4/4/01 11:16 AM Page 32
Содержание NRGD-4Q Series
Страница 9: ...vii Regenerative Drives Figure 1 Four Quadrant Operation...
Страница 12: ...x Notes...
Страница 15: ...3 Dimensions Figure 2 NRGD05 Series Dimensions ALL DIMENSIONS IN INCHES MILLIMETERS...
Страница 16: ...4 Dimensions Figure 3 NRGD10 Series Dimensions ALL DIMENSIONS IN INCHES MILLIMETERS...
Страница 17: ...5 Dimensions Figure 4 Heat Sink Dimensions for NRGD10 Series Drives...
Страница 33: ...21 Installation Figure 8 Regen Dump Circuit Connections To NRGD Drives...
Страница 57: ...45 Figure 15 Connection to DLC600 and PCM4 Application Notes Connection to other Minarik devices...
Страница 78: ...Notes...