10
Installation
Line fusing
Protect all Minarik drives with AC line fuses. Use fast acting AC
line fuses rated for 250 volts, and approximately 150% – 200% of
the maximum armature current. Fuse only the “hot” side of the
AC line (L1) if using 120 VAC line voltage. See Table 1 below
for recommended line fuse sizes.
Table 1. Recommended Line Fuse Sizes
90 VDC Motor 180 VDC Motor
Max. DC Armature
AC Line
Horsepower
Horsepower
Current (amps)
Size (amps)
1/20
1/10
0.5
2
1/15
1/8
0.8
2
1/8
1/4
1.5
3
1/6
1/3
1.7
5
1/4
1/2
2.5
8
1/3
3/4
3.5
8
1/2
1
5.0
10
3/4
1 1/2
7.5
15
1
2
10
20
Minarik Corporation offers two fuse kits: part number 050–0069
(3–8A Fuse Kit) and 050–0073 (5–20A Fuse Kit).
250-0281.qxd 4/4/01 11:16 AM Page 10