F3, F5, F9, FA, Fb, Fc, Fd: T6B/T6A/T5/T8/T9/TL/T7 Temperature sensor error
Digital display output
Description
F3 indicates subcooling gas temperature sensor (T6B) error.
F5 indicates injection liquid temperature sensor (T6A) error.
F9 indicates liquid pipe temperature sensor (T5) error.
FA indicates heat exchanger gas temperature sensor (T8) error.
Fb indicates heat sink temperature sensor (T9) error.
Fc indicates heat exchanger liquid temperature sensor (TL) error.
Fd indicates suction temperature sensor (T7) error.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Temperature sensor T6A/T6B/T5/T7/T8/T9/TL is open or short-circuited.
Recover condition: Temperature sensor T6A/T6B/T5/T7/T8/T9/TL connection ports can detect load.
Reset method: Resume automatically.
Possible causes
Temperature sensor not connected properly or has malfunction.
Damaged outdoor main PCB.