V6R VRF 50Hz
103
P
art
6
- Di
agno
si
s and
Tr
ou
bles
ho
o
ting
Procedure
H0
No
Communication wire from outdoor main
PCB CN26 to inverter module CN8/CN9 is
loosened.
1
Yes
Reconnect the communication wire.
No
Both LED1 and LED2 on inverter module
are off when power on.
2
Yes
Check the power supply circuit.
3
No
Replace the outdoor main PCB, is the
malfunction solved?
Yes
Normal.
No
Replace the inverter module
Yes
Normal.
No
Replace filter board.
Notes:
1.
Communication wire from outdoor main PCB CN26 to inverter module CN8/CN9.
Communication port CN26 on outdoor main PCB
Communication port CN8/CN9 on inverter module
2.
LED1/2 on inverter module
3.
Check the power supply for the compressor inverter module, the normal voltage L2 and N (CN4/CN6) 198v-242V.