V6R VRF 50Hz
66
Midea
V6R
Series S
er
vice M
anual
Table 5-2.5:
System check
DSP content
Parameters displayed on DSP2
Remarks
----
Standby (ODU a IDU Qty.)/frequency/particular state
0.--
Unit address
Master unit: 0; slave units: 1, 2
1.--
Single module capacity
8-18HP
2.--
Number of outdoor units
Displayed on master unit PCB only
3.--
Number of indoor units as set on PCB
Displayed on master unit PCB only
4.--
Total capacity of outdoor unit
Only available for master unit, displayed on slave
units has no sense
5.--
Single module compressor frequency
Displayed on master unit PCB only
6.--
System compressor frequency
Actual value = value displayed × 10
7.--
System operating mode
0: off; 2: cooling; 3: heating; 4: main heating; 5:
main cooling.
8.--
Fan A speed index
Refer to Note 1
9.--
Fan B speed index
Refer to Note 1
10.--
Indoor heat exchanger pipe (T2) temperature (°C)
Actual value = value displayed
11.--
Indoor heat exchanger pipe (T2B) temperature (°C)
Actual value = value displayed
12.--
Main heat exchanger pipe (T3) temperature (°C)
Actual value = value displayed
13.--
Outdoor ambient (T4) temperature (°C)
Actual value = value displayed
14.--
Outdoor liquid pipe (T5) temperature (°C)
Actual value = value displayed
15.--
Plate heat exchanger cooling refrigerant inlet (T6A) temperature (°C)
Actual value = value displayed
16.--
Plate heat exchanger cooling refrigerant outlet (T6B) temperature (°C)
Actual value = value displayed
17.--
Inverter compressor discharge (T7C1) temperature (°C)
Actual value = value displayed
18.--
Outdoor heat exchanger gas pipe (T5) temperature (°C)
Actual value = value displayed
19.--
Compressor inverter module internal (Ntc) temperature (°C)
Actual value = value displayed
20.--
Inverter module heatsink (T9)temperature (°C)
Actual value = value displayed
21.--
Outdoor heat exchanger liquid pipe (TL) temperature (°C)
Actual value = value displayed
22.--
Compressor suction (T7) temperature (°C)
Actual value = value displayed
23.--
Discharge superheat degree (°C)
Actual value = value displayed
24.--
Primary current (A)
Actual value = value displayed
25.--
EXVA position
Actual value = value displayed × 24
26.--
EXVC position
Actual value = value displayed × 4
27.--
Compressor discharge pressure (MPa)
Actual value = value displayed × 0.1
28.--
Compressor suction pressure (MPa)
Actual value = value displayed × 0.01
29.--
Number of indoor units currently in communication with master unit
Displayed on master unit PCB only
30.--
Number of indoor units currently operating
Displayed on master unit PCB only
31.--
Heat exchanger status
0-OFF; 1-Condenser; 2-Condenser (Not used);
3-Evaporator; 4-Evaporator (Not used)
32.--
System startup status
2~4-Startup control; 6-PI control;
33.--
Silent mode
Refer to Note 2
34.--
Static pressure mode
0: 0 Pa; 1: 20Pa; 2: 40Pa; 3: 60Pa; 4: 80Pa.
35.--
TES(°C)
Actual value = value displayed
36.--
TCS(°C)
Actual value = value displayed - 25
37.--
DC voltage A
Actual value = value displayed × 10
38.--
AC voltage B
Actual value = value displayed × 2
39.--
Number of indoor units for cooling operation
Actual value = value displayed
40.--
Number of indoor units for healing operation
Actual value = value displayed
41.--
Number of high temperature hydronic modules running
Actual value = value displayed
42.--
Total capacity of indoor units for cooling operation
43.--
Total capacity of indoor units for heating operation
44.--
Total capacity of high temperature hydro modules running
45.--
Fan's failure history
46.--
Software version
47.--
Power limitation mode settings
48.--
Reserved
49.--
Reserved
50.--
Reserved
51.--
Most recent error or protection code
“--“ is displayed if no error or protection events
have occurred since start-up
-- --
--
End
Notes:
1. The fan speed index is related to the fan speed in rpm and can take any integer value in the range 1 (slowest) to 30 (fastest).
2. Silent mode:
0: night silent time 6h/10h; 1: night silent time 6h/12h; 2: night silent time 8h/10h; 3: night silent time 8h/12h; 4: no silent mode; 5: silent mode;
6: super silent mode.
3.
Te: Low pressure equivalent saturation temperature (°C) Tes: Target Te value. Tc: High pressure equivalent saturation temperature (°C) Tcs: Target Tc value
.