Stop Operation
The stop operation occurs for one of the three following reasons:
1.
Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with
thermos-off' operation and an error code is displayed on the outdoor unit digital displays.
2.
The system stops when the set temperature of all indoor unit has been reached, or all indoor units has stop or error.
3.
The ambient temperature is greater than 30°C and the number of cooling Thermo ON indoor unit is 0.
Table 3-2.1: Component control during stop operation
Part Name
Symbol
Stop control
ODU
Inverter compressor A
INV1
OFF
Inverter fan 1
FANA
Keeps for 2 min, then OFF
Inverter fan 2
FANB
1
Four way valve
ST1
Holds
Electronic expansion valve
EEVA
0pls
EEVC
0pls
Solenoid valve
SV5
For single module: OFF
For combination module:
a. other module’s compressor ON, keeps for 2 min, then OFF
b. other module’s compressor OFF, OFF for 30S → ON for 1min → OFF
SV8A
For single module: OFF
For combination module:
a. other module’s compressor ON, keeps for 2 min, then OFF
b. other module’s compressor OFF, OFF
SV7
OFF for 1min → ON for 3min → OFF
MS04-MS12
Solenoid valve
SV(n)A
OFF
SV(n)B
OFF
SVP
OFF
Electronic expansion valve
EEVA
Keeps 0pls for 2 min, then 240pls
MS01
Electric ball valve
EBVA
0pls, then 500pls
EBVB
0pls, then 500pls
EBVC
0pls, then 500pls
Electronic expansion valve
EEVA
Keeps 0pls for 2 min, then 240pls