V6R VRF 50Hz
136
Midea
V
6R
Series S
er
vice M
anual
Procedure
P9 / H9
The capacity set on switch ENC2 on the
outdoor main PCB and the capacity given
on the unit’s nameplate do not match
Yes
Ensure the setting on switch ENC2
matches the unit capacity given on the
unit’s nameplate
No
Some power wires or communication
wires of fan module are not connected
properly
Yes
Ensure power and communication wires
are connected properly
No
The fan motor is blocked or has failed
Yes
Remove obstruction or replace the fan
motor
No
The power supply is abnormal
Yes
Check the power supply equipment
No
Replace the fan module resolves the
error
No
Replace the outdoor main PCB