H2, H3: Qty. of outdoor unit decreases/ increases error
Digital display output
Description
H2 indicates Qty. of outdoor unit decreases error.
H3 indicates Qty. of outdoor unit increases error.
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition
Trigger condition: Qty. of slave units detected by master unit has decreased or increased.
Recover condition: Qty. of slave units detected by master unit goes back to normal.
Reset method: Resume automatically.
Possible causes
Some outdoor units are powered off.
Power supply abnormal.
Incorrect outdoor unit address setting.
Communication wires between outdoor units not connected properly.
Loosened wiring within electric control box.
Damaged outdoor main PCB or electric control box communication terminals block.