V6R VRF 50Hz
31
P
art
3
- Con
tr
ol
5
Normal Operation Control
5.1
Component Control During Normal Operation
Table 3-5.1: Outdoor unit component control during normal operation
Component
Wiring
diagram label
Normal Cooling
Normal Heating
Normal Simultaneous
Cooling / Heating
Inverter compressor A
COMP(A)
PI control, High pressure protection, Low pressure protection, Discharge temperature
protection, Inverter Over-current protection control, Inverter module temperature
protection control, Wet compression protection control, High pressure ratio protection
control
DC fan motor A
FANA
PI control
PI control
PI control
DC fan motor B
*1
FANB
Electronic expansion valve A
EEVA
Subcooling control,
Inverter module
temperature control
Subcooling control,
Superheat control, Inverter
module temperature control
Subcooling control,
Superheat control,
Inverter module
temperature control
Electronic expansion valve C
EEVC
Superheat control
Superheat control
Superheat control
Four-way valve
ST1
Outdoor unit heat exchanger: Condenser / OFF
Outdoor unit heat exchanger: Evaporator / ON
Solenoid valve (fast
defrosting (in heating) and
unloading (in cooling))
SV5
ON with the following conditions:
Ambient temperature ≥5°C when heat exchanger act as evaporator or
when ambient temperature < 25°C when state of heat exchanger act as condenser
Solenoid valve (indoor units
bypass)
SV7
ON when the low pressure is too low or the high pressure is too high
Solenoid valve (inverter
compressor A vapor
injection)
SV8A
Compressor operation, ON
Compressor not operation, OFF
Table 3-5.2: Indoor unit component control during normal operation
Component
Normal cooling
Normal heating
Fan
Thermo ON unit
Remote controller setting
Remote controller setting
Stopping unit
OFF
OFF
Thermo OFF unit
Remote controller setting
Remote controller setting
Electronic
expansion
valve (EEV)
Thermo ON unit
Outlet temperature average control
Condensing temperature average control
Stopping unit
500P EEV IDU: 56pls
3000P EEV IDU: 72pls
500P EEV IDU: 56pls
3000P EEV IDU: 72pls
Thermo OFF unit
500P EEV IDU: 56pls
3000P EEV IDU: 72pls
500P EEV IDU: 56pls
3000P EEV IDU: 72pls