Procedure
F6
Electronic expansion valve coil
connection on MS main PCB is loose.
Yes
Ensure the valve coil is connected
properly
No
Electronic ball valve coil has
malfunction
1
.
Yes
Replace the coil.
No
Replace the MS main PCB
Notes:
1.
The normal resistances between EBV coil wiring terminals Gray (common port) and Blake / Yellow / Red / Orange are 40-50Ω. If any of the resistances differ
from the value, the EBV coil has malfunction.
Figure 6-2.4: EBV coil wiring terminals