3.5
FE: MS has no address when first powered on
Digital display output
Description
MS has no address when first powered on.
All units stop running.
Error code is displayed on the malfunction MS box.
The indoor unit display board or wire control connected to this MS displays "F8”.
Trigger / recover condition
Trigger condition: MS has no address when first powered on.
Recover condition: MS has got an address.
Reset method: Resume automatically.
Possible causes
The outdoor unit is not powered on or the address assignment is unsuccessful.
Procedure
FE
Select the nC4
1
outdoor unit menu to
enter the address automatically and
automatically assign the address to the
MS.
Notes:
1.
Refer to Part 5, 2.2.3 "Menu mode”