V6R VRF 50Hz
143
P
art
6
- Di
agno
si
s and
Tr
ou
bles
ho
o
ting
2.29
CA1, CA2, CA3, CA4, CA5: Connection combination error
Digital display output
Description
Connection combination error.
All units stop running.
Error code is only displayed on the master unit.
Trigger / recover condition
Trigger condition:
The types of inside equipment that can be connected to the V6R series heat recovery outdoor unit include:
•
Standard air-cooled indoor unit (Fresh air indoor unit is treated as standard indoor unit)
•
AHU KIT
•
High temperature hydraulic module HT
The following connection combinations are allowed:
•
VRF AHU KIT
•
VRF HT
•
VRF Indoor only
In addition to the above three cases, when the remaining connection combination is detected, the connection
combination failure is reported.
CA1
The system contains non-V6 series units (the highest priority).
CA2
Only AHU KIT.
CA3
Only HT
CA4
Only HT + AHU KIT
CA5
VRF AHU KIT + HT
Recover condition:
Detected correct combination.
Reset method: Manually restart.
Possible causes
Combination does not meet the requirements.
Procedure
CA1, CA2, CA3, CA4, CA5
Change indoor unit combination