Table 3-7.2: Indoor unit component control during oil return operation in cooling
only/main cooling mode
Cooling indoor unit
2000P EEV
500P EEV
FAN
Thermo ON unit
Keep the previous fan speed
Thermo OFF unit
Stop or Fan
Electronic expansion valve (EEV)
Thermo ON unit
Superheat control
Thermo OFF unit
1200pls
300pls
Stop or Fan
1200pls
300pls
Heating indoor unit (ODU operates cooling main operation)
2000P EEV
2000P EEV
FAN
(Set the controller to display E0, default)
Thermo ON unit
OFF
Thermo OFF unit
OFF
Stop
OFF
FAN
(Set the controller not to display E0)
Thermo ON unit
Low fan speed
Thermo OFF unit
Low fan speed
Stop
OFF
Electronic expansion valve (EEV)
(Set the controller to display E0, default)
Thermo ON unit
Within 2min: 1920pls
2-4min: 1200pls
After 4min: 480pls
Within 2min: 480pls
2-4min: 300pls
After 4min: 120pls
Thermo OFF unit
Stop or error stop
Electronic expansion valve (EEV)
(Set the controller not to display E0)
Thermo ON unit
0pls
0pls
Thermo OFF unit
Stop or error stop
Heating Oil Return Control
It’s basically identical with defrosting operation, refer to 7.2 Defrosting Operation