41
The others models:
Codes
Contents
E01
The temp. sensor is open or short-circuit.
E02
Compressor is over current
E04
Outdoor unit protection
P02
Compressor is over load
P03
The temperature of evaporator coil of indoor unit is too low (when coo
ling)
P04
The temperature of evaporator coil of indoor unit is too high (when he
ating)
P05
The temperature of air outlet of indoor unit is too high (when heating)
9.2 LEDs for the indication of outdoor trouble
In normal operation, LEDs emit no light and they will flash at a frequency of 2Hz w
hen trouble occurs. Their codes are listed in the following table:
MFE-60ARN1-RB4W (2T0043800036):
Type
Contents
LED2(green) LED3(yellow) LED4(red)
Normal
Normal running
Light
Off
Off
Normal
Normal standby
Off
Light
Off
Trouble
Phase sequence
Off
Flash
Off
Trouble
Lack of phase
Off
Off
Flash
Trouble
Protection of low pressure
Flash
Off
Flash
Trouble
Protection of high pressure
Flash
Flash
Off
Trouble
Overload of current
Off
Flash
Light
Trouble
Communication malfunction
Off
Flash
Flash
Trouble
Open- or short-circuit of T3
temperature sensor
Off
Off
Light
Trouble
Open- or short-circuit of T4
temperature sensor
Flash
Off
Off
Trouble
Discharge temperature protection of
compressor
Light
Off
Light
Trouble
High temperature protection of condenser
Flash
Flash
Light
Trouble
Fan jump selection error
Flash
Flash
Flash
The others models:
Type
Contents
LED1 LED2 LED3
Trouble
Phase sequence or Lack of phase(A ,B)
Flash
Off
Off
Содержание MFE-60AMN1-RB4W
Страница 6: ...3 2 Dimension 2 1 Indoor Unit Dimension Mode W mm D mm H mm 55K 600 358 1900...
Страница 9: ...6 4 Wiring diagram 4 1MFE 60AMN1 RB4W Indoor Unit Outdoor Unit...
Страница 10: ...7 4 2MFE 60ARN1 RB4W 2T0043800026 Indoor Unit Outdoor Unit...
Страница 11: ...8 4 3MFE 60ARN1 RB4W 2T0043800036 Indoor Unit Outdoor Unit...
Страница 49: ...46 9 3 8 Overload of current...
Страница 50: ...47 9 3 9 Indoor outdoor unit communication error...