34
-2
T1-Ts
-3
High
Low
-5
Medium
-4
The others modes:
8.3.2.4 Electric heaters (only available to some modes)
Electric heaters only opens in heating mode
MFE-60ARN1-RB4W(2T0043800036)
The others modes:
8.3.2.5 Defrost (only available to heating mode)
MFE-60ARN1-RB4W(2T0043800036)
---Defrosting Conditions
Starting Of Defrosting Condition (meet one of the following is ok):
(1)Accumulated time when temperature of outdoor heat exchanger coil T3 is below 3°C
reaches to 40 minutes, then consecutive 3 minutes less than -5 degrees (Just for the
AC is turn on , whether or not the heating mode the temperature was detected, start
to statistical time when reach the temperature condition . Shut down or defrosting
calculate time again).
(2) Accumulated time when temperature of outdoor heat exchanger coil T3 is below 3°C
reaches to 60 minutes, then consecutive 3 minutes less than -4 degrees (Just for the
AC is turn on , whether or not the heating mode the temperature was detected, start
to statistical time when reach the temperature condition . Shut down or defrosting
Condition
Fan speed
Ts-T
1≥4°C
High
2°C
≤Ts-T1 < 4°C
Med
Ts-T1 < 2°C
Low
Condition
Electric heaters
T4
<
5
℃
On
T4
>
7
℃
Off
Condition
Electric heaters
Ts-T1 > 6°C and indoor fan opens,T2 < 50 °C
On
T1≥Ts or indoor fan closes or T2 > 52 °C
Off
Содержание MFE-60AMN1-RB4W
Страница 6: ...3 2 Dimension 2 1 Indoor Unit Dimension Mode W mm D mm H mm 55K 600 358 1900...
Страница 9: ...6 4 Wiring diagram 4 1MFE 60AMN1 RB4W Indoor Unit Outdoor Unit...
Страница 10: ...7 4 2MFE 60ARN1 RB4W 2T0043800026 Indoor Unit Outdoor Unit...
Страница 11: ...8 4 3MFE 60ARN1 RB4W 2T0043800036 Indoor Unit Outdoor Unit...
Страница 49: ...46 9 3 8 Overload of current...
Страница 50: ...47 9 3 9 Indoor outdoor unit communication error...