37
The others modes:
When compressor is on, outdoor fan will follow the below rules:
When T3
≥
33
℃
, the two fan run at the same time.
When T3
≤
30
℃
, the above fan is on, the below fan is off.
8.3.3.2 Action of Indoor Fan
HIGH/ MED /LOW/AUTO fan can be switched over by your comfort.
Auto fan under cooling mode.
MFE-60ARN1-RB4W(2T0043800036)
5.0
4.0
High
Low
2.0
Medium
3.0
The others modes:
8.3.3.3 Low evaporator coil temperature T2 protection
MFE-60ARN1-RB4W(2T0043800036)
AC will enter T2 protection if any of the following conditions is satisfied.
Condition 1:
T2CoolExit
T2
On
Off
T2CoolIn
Condition
Compressor and outdoor fan
T1-Ts
≥1°C and compressor is off reac
hes up to over 3 minutes
On
Ts-T1>1°C
Off
Condition
Fan speed
T1-T
s≥4°C
High
2°C
≤ T1-Ts < 4°C
Med
T1-Ts < 2°C
Low