9.3.11 Indoor fan speed has been out of control
Shut off the power supply
and turn it on 5 seconds
later. Is it still displaying
the error code?
Shut off the power supply,
rotate the fan by hand.
Does it rotate properly?
The unit operates normally.
Find out the cause and
have it solved. For
example, check
whether the fan is
blocked or the bearing
is broken?
Check the wires of fan
motor. Are all the
connections good?
No
Yes
No
Correct the connections.
No
Yes
Yes
Check whether the fan
motor is normal through
index 1?
Replace the fan
motor
No
If the
malfunction is
still existing,
replace the
main PCB