33
8.3 Operation modes and functions
8.3.1 Manual operation
8.3.2 Heating mode
8.3.2.1 Four-way valve opens at once and anti-cold air function opens at the same time,
electric heaters starts or stops according to 8.3.2.4.
8.3.2.2 Condition for the compressor and outdoor fan action:
MFE-60ARN1-RB4W(2T0043800036)
When compressor is on, outdoor fan will follow the below rules:
Fan(below): When compressor is on, the outdoor fan runs all the time.
Fan(above):
18
T4
Off
On
16
The others modes:
When compressor is on, outdoor fan will follow the below rules:
When T4
≤
16
℃
, the two fan run at the same time.
When T4
≥
18
℃
, the below fan is on, the above fan is off.
8.3.2.3 Indoor fan action
Auto fan in heating mode
MFE-60ARN1-RB4W(2T0043800036):
Condition
Compressor and outdoor fan
Ts-T
1≥1°C
On
T1-Ts>0°C
Off
Condition
Compressor and outdoor fan(High)
Ts-T
1≥1°C and compressor is off
reaches up to over 4 minutes
On
T1-Ts>2°C
Off